beautypg.com

Danger, Caution, Installation – Oakworks Clodagh Libra User Manual

Page 9: Grounding, Facility electrical instructions

background image

This product must also be connected to a Ground Fault protected outlet with the detector in the main cir-

cuit breaker box (not on the circuit). (NOTE: GFCI ON THE TABLE ALONE IS NOT SUFFICIENT FOR

YOUR SAFETY.) If it should malfunction or break down, grounding provides a path of least resistance for

electrical current to reduce the risk of electric shock. This product is equipped with a cord having an equip-

ment-grounding conductor and a grounding pin. The pin must be plugged into an appropriate outlet that is
properly installed and grounded in accordance with all local codes and ordinances. See U.S. sample below.

Risk of Electric Shock - Connect this furnishing to a Ground Fault Protected Outlet only.

DaNGer

GroUNDING

The integral GFCI should be tested on a routine basis. To test the GFCI, push the test button. The GFCI

should interrupt power. Push the reset button. Power should be restored. If the GFCI fails to operate in

this manner, DO NOT USE THE UNIT. Disconnect the unit and have the problem corrected by a qualified

service representative or an electrician before using.
Improper connection of the equipment-grounding conductor can result in a risk of electric shock. Check

with a qualified electrician or service person if you are in doubt as to whether the product is properly

grounded. Do not modify the plug provided with the product - if it will not fit the outlet; have a proper
outlet installed by a qualified electrician.

Correct Implementation

Incorrect Implementation

Grounding Methods

6

INSTallaTIoN

faCIlITy eleCTrICal INSTrUCTIoNS

CaUTIoN

When installed in the United States, the electrical wiring of this table must meet the require-

ments of the National Electric Code (NEC) and any applicable state or local codes. The elec-

trical circuit providing 115V/15A power (230V overseas) to this table must be protected by a

GFCI (ground fault interrupter circuit) installed by a qualified electrician. Installation should be

approved by a local building/electrical/plumbing inspector.

Facility Connection Requirements:

1. An electrical circuit protected by a GFCI circuit breaker as required by state or local codes.

Procedure:

a. The table is equipped with a 3ft power cord which may be plugged into either a wall outlet or floor GFCI. If locat-

ed on the floor, the following location is recommended.

recommended

area for floor

installed GFCI

protected outlet

24”

6”

6”

19”