Danger, Caution, Installation – Oakworks Clodagh Libra User Manual
Page 9: Grounding, Facility electrical instructions
This product must also be connected to a Ground Fault protected outlet with the detector in the main cir-
cuit breaker box (not on the circuit). (NOTE: GFCI ON THE TABLE ALONE IS NOT SUFFICIENT FOR
YOUR SAFETY.) If it should malfunction or break down, grounding provides a path of least resistance for
electrical current to reduce the risk of electric shock. This product is equipped with a cord having an equip-
ment-grounding conductor and a grounding pin. The pin must be plugged into an appropriate outlet that is
properly installed and grounded in accordance with all local codes and ordinances. See U.S. sample below.
Risk of Electric Shock - Connect this furnishing to a Ground Fault Protected Outlet only.
DaNGer
GroUNDING
The integral GFCI should be tested on a routine basis. To test the GFCI, push the test button. The GFCI
should interrupt power. Push the reset button. Power should be restored. If the GFCI fails to operate in
this manner, DO NOT USE THE UNIT. Disconnect the unit and have the problem corrected by a qualified
service representative or an electrician before using.
Improper connection of the equipment-grounding conductor can result in a risk of electric shock. Check
with a qualified electrician or service person if you are in doubt as to whether the product is properly
grounded. Do not modify the plug provided with the product - if it will not fit the outlet; have a proper
outlet installed by a qualified electrician.
Correct Implementation
Incorrect Implementation
Grounding Methods
6
INSTallaTIoN
faCIlITy eleCTrICal INSTrUCTIoNS
CaUTIoN
When installed in the United States, the electrical wiring of this table must meet the require-
ments of the National Electric Code (NEC) and any applicable state or local codes. The elec-
trical circuit providing 115V/15A power (230V overseas) to this table must be protected by a
GFCI (ground fault interrupter circuit) installed by a qualified electrician. Installation should be
approved by a local building/electrical/plumbing inspector.
Facility Connection Requirements:
1. An electrical circuit protected by a GFCI circuit breaker as required by state or local codes.
Procedure:
a. The table is equipped with a 3ft power cord which may be plugged into either a wall outlet or floor GFCI. If locat-
ed on the floor, the following location is recommended.
recommended
area for floor
installed GFCI
protected outlet
24”
6”
6”
19”