Responding to Audible Alarms
Acknowledgement Audible Alarm
Table 6-1
Acknowledgement Audible Alarm
Audible Alarm Group
Audible Alarm Sound
Cause(s)
Action
Acknowledgement
Single short beep.
The ON or TEST button
was pressed.
No action needed.
The self or battery test
completes successfully.
No action needed.
Shutdown Imminent Audible Alarm
Table 6-2
Shutdown Imminent Audible Alarm
Audible Alarm Group
Audible Alarm Sound
Cause(s)
Action
Shutdown Imminent
Single long beep.
Heat sink
over temperature
while on battery.
UPS will shut down in 3
seconds. Contact an
authorized service provider.
Remote Emergency
Power Off.
(Switch “closed,” or
input low.)
Check position of REPO
switch. Open the REPO
switch.