beautypg.com

Compaq R6000 Series User Manual

Page 78

background image

Configuration 4-21

Compaq Confidential – Need to Know Required

Writer: Daniel E. Lyons Project: Compaq R6000 Series UPS Operation and Reference Guide Comments: Revised as per A. May

Part Number: 347223-022 File Name: e-ch4.doc Last Saved On: 3/24/99 1:44 PM

Set Voltage

The Compaq R6000 UPS must be placed in manual Bypass using the switch at
the rear of the unit, and placed into Standby mode (see Chapter 3,
“Operation”) to set the voltage.

The voltage that is set will appear with an “*”. Using the Center button, scroll
through the voltages and choose using the Enter button. The choices are:

200 V

208 V

220 V

230 V

240 V

208/230 V Auto Sensing

230 V Extended

Set Voltage

208V

Set Site Fault

The two values are “Disable” or “Enable.” Use the Center button to scroll and
the Enter button to select. An asterisk, “*” marks the selected value.

Set Site Fault

Enable

Set Sleep Mode

When Sleep Mode is enabled, if the UPS is supplying battery power and the
load on the UPS is less than 8%, the UPS switches to Sleep mode (the UPS
shuts itself off). Use the Center and Enter buttons to “Enable” or “Disable”
this feature. An “*” will mark the selected value.

Set Sleep Mode

Enable