4-10 Compaq R6000 Series UPS Operation and Reference Guide

Compaq Confidential – Need to Know Required

Writer: Daniel E. Lyons Project: Compaq R6000 Series UPS Operation and Reference Guide Comments: Revised as per A. May

Part Number: 347223-022 File Name: e-ch4.doc Last Saved On: 3/24/99 1:44 PM

Active Alarms

Main Menu

Active Alarms

When an alarm sounds (and the red LED lights), from the Main Menu, scroll
to the active alarm count. “X” is the number of alarms detected. Press the
Enter button to step through the list of alarm descriptions. If more than 1
alarm was indicated, make sure to look at every alarm.

The alarms generated by this UPS are:

Input AC Over Voltage

If the utility voltage rises over the specified range, the UPS will buck the
output voltage down, and trigger a red LED alarm signal. An audible alarm
will be triggered when overvoltage reaches 120% of the nominal range setting.

X Alarms

Input AC Over Voltage

Input AC Under Voltage

If the utility voltage falls below the specified range (20% or more under
voltage), the UPS will boost the output voltage up and raise an alarm. This
alarm will not appear until the UPS is on battery.

X Alarms

Input AC Under Voltage

Input Over or Under Frequency

If the utility frequency suddenly changes, the UPS will raise an alarm. This
only occurs when the UPS goes on battery.

X Alarms

Input Over or Under Frequency