2-10 Compaq R6000 Series UPS Operation and Reference Guide

Compaq Confidential – Need to Know Required

Writer: Dan Lyons Project: Compaq R6000 Series UPS Operation and Reference Guide Comments: revised as per A. May

Part Number: 347223-022 File Name: c-ch2.doc Last Saved On: 3/24/99 1:41 PM

Recommendation

Flexible metal conduit should be used when hardwiring the Compaq R6000
UPS. This will provide ease of service and maintenance of the system. Please
consult a licensed electrician.

Procedure

1.

Locate the input wiring entry port (1),input wiring inspection panel
(2), and terminal block input cover (3).

NORMAL

BYPASS

13842

5244-0

01 RE

V. P00

1
&
4

2

1

4

2

3

5

5

5

5

3

3

2

2

2

3

1

1

1

4

4

4

3

1

2

3

Figure 2-4. Rear panel, showing wiring entry point and inspection panel

2.

Remove the terminal input block cover. Set aside but do not discard the
cover; the input block cover carries the wiring diagram for the terminal
block.