Battery specifications, Battery runtime – Compaq R6000 Series User Manual
Page 112
Specifications C-5
Compaq Confidential – Need to Know Required
Writer: Daniel E. Lyons Project: Compaq 6000 Series UPS Operation and Reference Guide Comments:
Part Number: 347223-xx1 File Name: j-appc.doc Last Saved On: 2/14/99 3:53 PM
Battery Specifications
Table C-4
Battery Specifications
Feature
Specification
Type
Sealed lead-acid; maintenance-free
Voltage
Internal batteries - 12 VDC each, 360 VDC total
Charging
24 hours to full charge
4 hours to 90% capacity at default nominal utility
voltage and no load
Battery Runtime
Table C-5
Load Effect on Backup Time
Load %
Estimated Backup Time
100
Greater than 6 minutes
80
Greater than 8 minutes
50
Greater than 15 minutes
80% plus 1 ERM
Greater than 18 minutes
80% plus 2 ERMs
Greater than 30 minutes