Compaq R6000 Series User Manual
Page 73

4-16 Compaq R6000 Series UPS Operation and Reference Guide
Compaq Confidential – Need to Know Required
Writer: Daniel E. Lyons Project: Compaq R6000 Series UPS Operation and Reference Guide Comments: Revised as per A. May
Part Number: 347223-022 File Name: e-ch4.doc Last Saved On: 3/24/99 1:44 PM
Battery Setup
This menu provides a means to set the Amp-Hour Rating of each cabinet, or
configure the number of external battery cabinets.
Even though the menu allows settings from 1-25, choose 5 A-H for the UPS
batteries, and 5 A-H for each additional ERM, using the Center and Enter
buttons.
An asterisk, “*” appears by the selected value.
Battery Amp-Hr
Internal
0-25
Set Language
The Set Language menu provides a means to select from eight different
languages for the menu display, using the Center and Enter buttons. The
asterisk (*) shows the current configuration.
Set Language
∗
English
The available choices are:
■
Danish
■
Dutch
■
English
■
French
■
German
■
Spanish
■
Italian
■
Japanese