TABLETOP OR SHELF INSTALLATION

This section provides guidelines for installation on a tabletop or shelf.

Tabletop and shelf installations must be within reach of the network
cabling and meet the requirements listed below:

In a shelf installation, the shelf must be able to support 30 pounds of
static weight for each device in the stack.

Maintain a temperature of between 5

°

C (41

°

F) and 40

°

C (104

°

F) at

the installation site with fluctuations of less than 10

°

C per hour.

The SEHI must be located within seven feet of its power source and with
an unrestricted free surface area as shown in Figure 4-2.

Figure 4-2

Tabletop or Shelf Installation

Proceed to Section 4.5, Powering Up and Stacking the SEHI.

4.4

RACKMOUNT INSTALLATION

To install the SEHI in a 19-inch rack, Cabletron Systems provides a kit
with the SEHI that includes rackmount brackets, mounting screws, and a
strain-relief bracket for cable management.

!

CAUTION

In order to allow for proper cooling, there must be a two-inch
clearance on either side and the back of the unit.

21 IN.

6 IN.

18 IN.

7 FT.