c. Suction-tube temperature (F) at low-side service

fitting.

d. Suction (low-side) pressure (psig).

5. Using ‘‘Superheat Charging Table,’’ compare outdoor-air

temperature (F db) with evaporator inlet-air temperature
(F wb) to determine desired system operating superheat
temperature. See Tables 5A-5I and 6A-6F.

6. Using

‘‘Required

Suction-Tube

Temperature

(F)’’

table, compare desired superheat temperature with suc-
tion (low-side) operating pressure (psig) to determine proper
suction-tube temperature. See Table 7.

7. Compare actual suction-tube temperature with proper

suction-tube temperature. Using a tolerance of ±3° F, add
refrigerant if actual temperature is more than 3° F higher
than proper suction-tube temperature, or remove refrig-
erant if actual temperature is more than 3° F lower than
required suction-tube temperature.

NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to Check for Refrigerant Leaks sec-
tion on page 27.

Table 5A — Superheat Charging Table, 50SS018

TEMP (F)

AIR ENT

COND

EVAP AIR — CFM

600

Evap Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

17.3

18.5

19.6

20.8

24.2

27.7

28.5

29.3

29.3

29.3

29.3

29.3

70

SPH

13.8

14.9

16.1

17.3

20.7

24.1

25.7

27.3

27.3

27.3

27.3

27.3

75

SPH

10.2

11.4

12.5

13.7

17.1

20.6

22.9

25.2

25.2

25.2

25.2

25.2

80

SPH

8.2

8.8

9.5

10.2

13.6

17.0

20.1

23.1

23.9

24.1

25.4

26.1

85

SPH

6.1

6.2

6.5

6.6

10.0

13.5

17.3

21.1

22.6

24.1

25.6

27.1

90

SPH

*

*

*

5.0

8.1

11.4

15.2

19.0

20.5

22.0

23.5

25.0

95

SPH

*

*

*

*

6.2

9.4

13.2

17.0

18.5

20.0

21.5

23.0

100

SPH

*

*

*

*

*

7.3

11.1

14.9

17.2

19.5

21.7

24.0

105

SPH

*

*

*

*

*

5.3

9.1

12.9

15.9

18.9

21.9

24.9

110

SPH

*

*

*

*

*

*

6.7

10.8

13.8

16.8

19.8

22.8

115

SPH

*

*

*

*

*

*

*

8.8

11.8

14.8

17.8

20.8

LEGEND

Ewb — Entering Wet Bulb

SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant slugging may occur.

Table 5B — Superheat Charging Table, 50SS024

TEMP (F)

AIR ENT

COND

EVAP AIR — CFM

800

Evap Air — Ewb (F)

54

56

58

60

62

64

66

68

70

72

74

76

65

SPH

18.2

19.0

19.9

20.7

22.5

24.2

25.1

25.9

26.6

27.2

27.9

28.6

70

SPH

17.1

17.6

18.1

18.6

20.4

22.1

23.0

23.9

24.9

26.0

27.1

28.1

75

SPH

16.0

16.2

16.4

16.6

18.3

20.1

21.0

21.8

23.3

24.8

26.2

27.7

80

SPH

14.8

14.7

14.6

14.5

16.3

18.0

19.7

21.3

22.4

23.5

24.6

25.8

85

SPH

13.7

13.3

12.9

12.5

14.3

16.0

18.4

20.7

21.5

22.3

23.1

23.8

90

SPH

11.1

10.9

10.7

10.4

12.2

13.9

16.3

18.7

19.9

21.0

22.2

23.4

95

SPH

8.5

8.4

8.4

8.4

10.1

11.9

14.3

16.6

18.2

19.8

21.4

23.0

100

SPH

7.3

7.5

7.7

7.9

8.9

9.9

12.2

14.6

16.6

18.6

20.6

22.6

105

SPH

6.2

6.6

6.9

7.3

7.6

7.8

10.2

12.5

14.9

17.3

19.7

22.1

110

SPH

*

*

*

5.3

5.5

5.8

8.1

10.5

13.3

16.1

18.9

21.7

115

SPH

*

*

*

*

*

*

6.1

8.4

11.6

14.9

18.1

21.3

LEGEND

Ewb — Entering Wet Bulb
SPH — Superheat at Compressor (F)

*Do not attempt to charge system under these conditions — refrigerant slugging may occur.