beautypg.com

Step 6 — provide for condensate disposal – Carrier 50SX024-060 User Manual

Page 20

background image

ACCESSORY DUCT FLANGE KIT INSTALLATION —
Refer to Fig. 26 for duct adapter dimensions and hole
locations.
1. Mark hole locations shown in Fig. 26.
2. At marked locations, drill holes using a no. 26 (.147-in.)

twist drill.

3. Partially secure duct flanges using two of the no. 10,

1

2

-in.

screws provided.

4. See the following caution. Using remaining holes in duct

flanges as templates, drill the remaining holes with the
no. 26 (.147-in.) drill.

Do not drill deeper than

1

2

-in. into shaded area shown

in Fig. 26. Damage to refrigerant coil could result.

5. Fully secure the duct flanges using the remaining screws

provided.

The finished kit installation accommodates a 14

3

4

-in. x

14

3

4

-in. duct.

Step 6 — Provide for Condensate Disposal

NOTE: Be sure that condensate-water disposal methods com-
ply with local codes, restrictions, and practices.

Unit disposes of condensate through a

3

4

-in. NPT fitting

which exits through the compressor access panel. See
Fig. 2-9 for location of condensate connection.

Condensate water can be drained directly onto the roof in

rooftop installations (where permitted) or onto a gravel apron
in ground-level installations. Install a field-supplied conden-
sate trap at end of condensate connection to ensure proper
drainage. Make sure that the outlet of the trap is at least
1 in. lower than the drain-pan condensate connection to pre-
vent the pan from overflowing. See Fig. 27. Prime the trap
with water. When using a gravel apron, make sure it slopes
away from the unit.

If the installation requires draining the condensate water

away from the unit, install a 2-in. trap using a

3

4

-in. FPT

connection. See Fig. 27. Make sure that the outlet of the trap
is at least 1 in. lower than the unit drain-pan condensate con-
nection to prevent the pan from overflowing. Prime the trap
with water. Connect a drain tube using a minimum of

3

4

-in.

PVC,

3

4

-in. CPVC, or

3

4

-in. copper pipe (all field supplied).

Do not undersize the tube. Pitch the drain tube downward at
a slope of at least 1 in. for every 10 ft of horizontal run. Be
sure to check the drain tube for leaks. Prime trap at the be-
ginning of the cooling season start-up.

PLUG ASSEMBLIES

RACEWAY

FILLER
BRACKET

BLOWER
SHELF

Fig. 24 — Filler Bracket and Blower Shelf

HORIZONTAL DUCT OPENING

Fig. 25 — Housing Placed for Vertical Airflow

NOTE: Do not drill more than

1

2

-in. deep in shaded area.

Fig. 26 — Duct Flange Kit — Locating Holes

(Typical)

20

This manual is related to the following products: