Manual MCS-64: Modbus on Ethernet
Page 9
4 M
ODBUS
M
APPING
The MBAP header “Unit Identifier” field is used to select a module in the backplane. Address 0
(zero) is reserved for broadcast. Address 1 to 64 is then used for direct communication with any
LDM in the backplane using registers in the range 2000-2FFF (hex). Access to the gateway
should use address 0xFF (255 dec) and registers in the range 3000-3FFF(hex).
Currently implemented function codes are:
Access
03
Read Holding Registers
04
Read Input Registers
06
Write Single Register
16
Write Multiple Registers
Used exception codes are:
Meaning
01
Illegal or unkown function code
02
Illegal data address or no response from LDM
4.1 Modbus Register Map Overview
Register Type
Size
Access
Function
2000 – 2FFF
Selected LDM
3000 – 30FF
Gateway
4.1.1 Gateway Register Map
Register
Type Size Access
Function
3000
Int16
1
R/W
LDM selector [0..63]
3001
Int16
1
R/W
LDM multiple register selector.
3002
Int16
1
R/W
LDM multiple register mode
3003 – 300F
-
-
(reserved)
3005 Int16
1
R/W
Auto-Scan Control/Status
Bit:
15 10 9 2 1
+------------+--------+-----+
| Last scan | unused | R/S |
+------------+--------+-----+
3006
Int16
1
R/W
Auto-Scan Port (IP port no.)
3007
Int32
2
R/W
Auto-Scan Interval (ms)
3009 – 30FF
(reserved)
3100 – 31FF
R/W
Multiple register access across multiple LDM modules.
3200 – 32FF
Float
2+2+1
R
Multiple read of LDM packets
3300 – 33FF
Integer
2+2+1
R
Multiple read of LDM packets