Manual MCS-64: Modbus on Ethernet

Page 9

4 M

ODBUS

M

APPING

The MBAP header “Unit Identifier” field is used to select a module in the backplane. Address 0
(zero) is reserved for broadcast. Address 1 to 64 is then used for direct communication with any
LDM in the backplane using registers in the range 2000-2FFF (hex). Access to the gateway
should use address 0xFF (255 dec) and registers in the range 3000-3FFF(hex).


Currently implemented function codes are:

Access

03

Read Holding Registers

04

Read Input Registers

06

Write Single Register

16

Write Multiple Registers


Used exception codes are:

Meaning

01

Illegal or unkown function code

02

Illegal data address or no response from LDM

4.1 Modbus Register Map Overview

Register Type

Size

Access

Function

2000 – 2FFF

Selected LDM

3000 – 30FF

Gateway

4.1.1 Gateway Register Map

Register

Type Size Access

Function

3000

Int16

1

R/W

LDM selector [0..63]

3001

Int16

1

R/W

LDM multiple register selector.

3002

Int16

1

R/W

LDM multiple register mode

3003 – 300F

-

-

(reserved)

3005 Int16

1

R/W

Auto-Scan Control/Status

Bit:
15 10 9 2 1
+------------+--------+-----+

| Last scan | unused | R/S |
+------------+--------+-----+

3006

Int16

1

R/W

Auto-Scan Port (IP port no.)

3007

Int32

2

R/W

Auto-Scan Interval (ms)

3009 – 30FF

(reserved)

3100 – 31FF

R/W

Multiple register access across multiple LDM modules.

3200 – 32FF

Float

2+2+1

R

Multiple read of LDM packets

3300 – 33FF

Integer

2+2+1

R

Multiple read of LDM packets