Page 27
Manual MCS-64: Modbus on Ethernet
Page 27
Example of positive hysteresis of 100 kg (H1 = +1.00) on a setpoint of 20.00 kg (lines 3 & 4 of
table above):
When the weight is increasing between 0 kg and 19.99 kg the setpoint is “OFF”. Once the weight
increases above 19.99 kg then the setpoint is “ON”. The setpoint will switch “OFF” again when
the weight value drops below 19.00 kg.
An
Request/set the base for setpoint n; with n = 1, 2, 3 or 4
Source of the selected setpoint
[ Register = 2068, Type = Int32 ]
Request / Set base for setpoint 1
Master (PC / PLC) sends
Device responds
Result
A1 1+00000
Allocation gros weight
A1_1 OK
Allocation net weight
Similarly to read or set the setpoint 1 base, use A2 instead of A1 etc.
The A1 command defines the base on which the setpoint value acts. If A1 is set to “0” then
setpoint 1 acts on the unfiltered gross weight. If A1 is set to “1” then setpoint 1 acts on the
unfiltered net weight.
A1 = 0
Not filtered gross weight
A1 = 1
Not filtered net weight
NOTE: All changes to the setpoint settings have to be stored in the EEPROM using the SS
command. See section 4.11 page 4x.