beautypg.com

Flintec MCS-64 ModbusOnEthernet User Manual

Page 18

background image

Page

18

Manual MSC-64: Modbus on Ethernet

AZ

Absolute zero point calibration

[ Register = 2202, Type = Int32 ]

The command AZ is used as reference point for all weight calculations and will setup in mV/V.
Permitted values are ± 32000 (= ± 3.2000 mV/V).

Master (PC / PLC) sends

Device responds

Result

AZ

Z+0.0005

Request:

Zero point @ 0.0005mV/V

CE

E+00017 (example)

Request: TAC-counter CE 17

CE_17 OK

Calibration sequence active

AZ_00500 OK

Setting:

new: Zero point @ 0.0500 mV/V

Factory default: 00000 @ 0.0000 mV/V input signal.


AG

Absolute gain calibration

[ Register = 2200, Type = Int32 ]

The command AG is used as absolute gain (or measuring range) for all weight
calculations and will setup in mV/V. Permitted values are ± 32000 (= ± 3.2000 mV/V).

Master (PC / PLC) sends

Device responds

Result

AG

G+2.0000

Request:

Meas. range 2.000 mV/V

CE

E+00017 (example)

Request: TAC-counter CE 17

CE_17 OK

Calibration sequence active

AG_19998_90900

OK

new: Measuring range

1.9998 mV/V @ 90900 d

Factory default: 200000 @ 2.0000 mV/V input signal.

If the AG value has to be set at 2.0000 mV/V, but the load cell capacity is quoted at 2.2 mV/V,
you will have to ratio the load cell capacity down.

Example : A 100kg load cell with an Output at Rated Load of 2.2 mV/V would be equivalent to
90.9 kg @ 2 mV/V (exact 1.9998 mV/V)


ZT Zero

tracking

[ Register = 2122, Type = Int32 ]

This command enables or disables the zero tracking. Parameter = 0 disables the zero tracking
and parameter = 1 enables the zero tracking. Issuing the command without any parameter
returns the current ZT value.

Master (PC / PLC) sends

Device responds

Result

ZT Z:001

Request: ZT status (ON)

CE

E+00017 (example)

Request: TAC-counter CE 17

CE_17 OK

Calibration sequence active

ZT_0 OK

Setting: ZT = OFF

Zero tracking will be performed only on results less than +/-0.5 d at a rate of 0.4 d/sec, where d =
display step size (see DS command). The zero can only be tracked to +/- 2% of maximum (see
CM command).

In non legal for trade applications you can exceed the limit +/- 2%. If you require for example a
zero tracking range of +/- 10 d then you have to set ZT to be 100 where d is the division size
(which means d * 10).
Factory default: ZT=0