Manual MSC-64: Modbus on Ethernet
4.1.2 LDM Register Map
The register map for each LDM.
LDM overview
Register Type
Size
Access
Function
2000 – 201F
Float
08 * 2
R
/W
Data in Float Format
2020 – 205F
Int32
16 * 2
R
/W
Data in Integer Format
2060 – 207F
Int16
08 * 1
RW
Control/Status functions
2080 – 20FF
(reserved)
2100 – 2FFF
-
-
R/W
Parameter pages
Data in Float Format
Register Type Size Access Data
in
Float
Format
2000 Float
2 R
Gross
weight
2002 Float
2 R
Net
Weight
2004 Float
2 R/W Tare
2006 Float
2 R
Dosed
weight
2008 Float
2 R
Average
weight
Data in Integer Format
Register
Type
Size
Access
Data in Integer Format
2020 Int32
2 R
Gross
weight
2022 Int32
2 R
Net
Weight
2024 Int32
2 R/W Tare
2026 Int32
2 R
Dosed
weight
2028 Int32
2 R
Average
weight
202A Int32
2 R
A/D
sample
202C Int32
2 R
Device
ID
202E Int32
2 R
FW
Version
2030 Int32
2 R
Device
Status
2032 Int32
2 R
ADC
Reference
Control/Status Functions
Register Type Size Access Control/Status functions
2060
Int16
1
R
Measurement Qualifier Values:
$0001 - Under range
$0002 - Over range
$0004 - Not within Zero range (not yet implemented, zero)
$0008 - Exactly zero
$0010 - No motion, still stand, steady state
$0020 - Tare set
$0040 - Preset tare (0=tare is measured, 1=tare is set by user)
$0080 - Invalid weighing (wire-break, A/D ref. out of range)
$0100 - Set-point 0 (source>limit)
$0200 - Set-point 1
$0400 - Set-point 2
$0800 - Set-point 3
$1000 - Filling in progress
$2000 - Filling has completed
$4000 - Average ready
$8000 - Cold start