Flintec MCS-64 ModbusOnEthernet User Manual
Page 31
Manual MCS-64: Modbus on Ethernet
Page 31
5.9 Trigger Special Commands– RW, TT, TS, DT, TW, TI, HT
Remark: These commands are
only available in firmware 88.183 (see time diagram page 33).
Note: All setups should be stored with the WP command before power off.
RW
Re-Trigger Window
[ Register = 2404, Type = Int32 ]
Set the re-trigger window in counts (digits) without decimal point.
If the weight relative to the
current average value changes by more than the RW value the average cycle will be restarted
using TT as measuring time.To automatically issue the re-trigger command, the time period over
which an increase of weight average is measured has to be defined by using the command DT.
Master (PC / PLC) sends
Device responds
Result
RW R+65535
Request: RW=65535
RW_500 OK
Setting: RW=500d
Factory default: 65535
TT
Re-Trigger Time
[ Register = 2406, Type = Int32 ]
Set the re-trigger time in milliseconds [ms].
Re-trigger time is the average time used by the re-
trigger function. If set to zero the re-trigger function is disabled.
Master (PC / PLC) sends
Device responds
Result
TT T+65535
Request: TT=65535
TT_300 OK
Setting: TT=300ms
Factory default: 65535
TS
Re-Trigger Stop
[ Register = 240E, Type = Int32 ]
Set the re-trigger stop in counts (digits) without decimal point.
In case of a (TS) decrease in
weight relative to the current average value the re-trigger function is stopped.
Master (PC / PLC) sends
Device responds
Result
TS T+00000
Request: TS=00000
TS_480 OK
Setting: TT=480d
Factory default: 00000
DT
Delta Time
[ Register = 2414, Type = Int32 ]
Set the Delta Time in milliseconds [ms].
During MT and TT timeframes "sub-averages" will be
calculated by the system over the time DT. If a sub-average is outside the re-trigger window, the
re-trigger function is automatic started.
Master (PC / PLC) sends
Device responds
Result
DT T+00000
Request: DT=00000
DT_50 OK
Setting: TT=50ms
Factory default: 00000