EVCO EC6295S201 User Manual
Page 6
10
WORKING SETPOINT AND CONFIGURATION PARAMETERS
10.1 Working setpoint
LABEL MIN. MAX. U.M.
DEF. WORKING SETPOINT
r1
r2
°C/°F
(5)
0.0
working setpoint
10.2 First level parameters
LABEL MIN. MAX. U.M.
DEF. PASSWORD
PA
-55
99
---
0
password
LABEL MIN. MAX. U.M.
DEF. MEASURE INPUTS
/1A
-10
10.0 °C/°F
(5)
0.0
cabinet probe calibration
/1b
-10
10.0 °C/°F
(5)
0.0
first evaporator probe calibration
/1C
-10
10.0 °C/°F
(5)
0.0
second evaporator probe calibration
LABEL MIN. MAX. U.M.
DEF. REGULATOR
r0
0.1
15.0 °C/°F
(5)
2.0
hysteresis (differential, it is relative to the working setpoint)
LABEL MIN. MAX. U.M.
DEF. SERIAL NETWORK (EVCONET)
n3
0
1
---
0
authorization to implement the remote controls coming from the master (it is important if
n0 = 2 and n1 ≠ 0; 1 = YES)
LABEL MIN. MAX. U.M.
DEF. ENERGY SAVING (the working setpoint becomes r8)
Hr1
0.0
23.5 h.damin
(6)
0.0
Energy Saving cycle activation time
Hr2
0.0
23.5 h.damin
(6)
0.0
Energy Saving cycle length
LABEL MIN. MAX. U.M.
DEF. REAL TIME DEFROST
Hd1 0.0
23.5 h.damin
(6)
- - -
first defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd2 0.0
23.5 h.damin
(6)
- - -
second defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd3 0.0
23.5 h.damin
(6)
- - -
third defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd4 0.0
23.5 h.damin
(6)
- - -
fourth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd5 0.0
23.5 h.damin
(6)
- - -
fifth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
Hd6 0.0
23.5 h.damin
(6)
- - -
sixth defrost activation time (it is important if dE = 3; - - - = it will never be activated)
(7)
10.3 Second level parameters
LABEL MIN. MAX. U.M.
DEF. MEASURE INPUTS
/0
1
3
---
1
kind of probe (1 = PTC, 3 = NTC)
/1A
-10
10.0 °C/°F
(5)
0.0
cabinet probe calibration
/1b
-10
10.0 °C/°F
(5)
0.0
first evaporator probe calibration
/1C
-10
10.0 °C/°F
(5)
0.0
second evaporator probe calibration
/5
0
1
---
1
temperature resolution (it is important if /8 = 1; 0 = 1 degree, 1 = 0.1 degrees)
/8
0
1
---
1
temperature unit of measure (0 = Fahrenheit degree, 1 = Celsius degree)
LABEL MIN. MAX. U.M.
DEF. REGULATOR
r0
0.1
15.0 °C/°F
(5)
2.0
hysteresis (differential, it is relative to the working setpoint)
r1
-99
r2
°C/°F
(5)
-50
minimum value you can assign to the working setpoint
r2
r1
99.9 °C/°F
(5)
50.0 maximum value you can assign to the working setpoint
r5
0
1
---
0
working setpoint modification lock-out (1 = YES)
r8
-99
99.9 °C/°F
(5)
0.0
auxiliary working setpoint (it is the working setpoint during the multifunction input activa-
tion if i0 = 6 or 7 and during the Energy Saving cycle)
LABEL MIN. MAX. U.M.
DEF. COMPRESSOR PROTECTION
C0
0
240
min
0
minimum delay between you turn the instrument ON and the first compressor activation
C1
0
240
min
5
minimum delay between two compressor activation in succession
C2
0
240
min
3
minimum delay between the compressor gets OFF and the following activation
C4
0
1
---
0
fixed delay since the compressor gets ON and OFF (1 = YES, for 3 s)
C5
1
240
min
10
cycle time for the compressor activation during the cabinet probe alarm
C6
0
100
%
50
percentage of C5 the compressor is ON during the cabinet probe failure
(8)
LABEL MIN. MAX. U.M.
DEF. DEFROST
d0
0
99
h
8
defrost interval (it is important if dE ≠ 3); look at dE as well
(7)
(0 = the defrost will never
automatically be activated)
d1
0
1
---
1
kind of defrost (0 = electric defrost, 1 = hot gas defrost)
d2
-99
99.9 °C/°F
(5)
2.0
defrost end temperature (evaporators temperature)
(9)
d3
0
99
min
30
defrost maximum length (0 = the defrost will never be activated)
d4
0
1
---
0
defrost activation every time you turn the instrument ON (1 = YES)
(7)
d5
0
99
min
0
delay between you turn the instrument ON and the defrost activation (it is important if
d4 = 1)
d6
0
1
---
1
freeze of the temperature showed by the instrument during the defrost (1 = YES)
(10)
d7
0
15
min
2
dripping time
d9
0
1
---
0
compressor protections cleaning at the moment of the defrost activation (it is important if
d1 = 1; 1 = YES)
dE
0
3
---
0
defrost interval count mode; look at d0 as well (0 = the instrument counts the working time,
1 = the instrument counts the sum of the times the compressor is ON,
2 = the instrument counts the sum of the times at least one of the two evaporator tempera-
tures is below dF, 3 = real time defrost, the defrost will be activated at the times you have set
with the parameters Hd1 ... Hd6)
dF
-99
99.9 °C/°F
(5)
0.0
defrost interval count freeze threshold (evaporators temperature, it is important if dE = 2)