A3

0

2

- - - -

0

0

A4

0

999

°C/°F (1)

not visible

0

A5

0

240

min

not visible

0

A6

0

2

- - - -

not visible

0

PARAM. MIN.

MAX.

U.M.

1 INPUT

2 INPUTS

i1

0

1

- - - -

0

0

i5

0

6

- - - -

0

0

i6

0

1

- - - -

0

0

i7

0

120

min

0

0

PARAM. MIN.

MAX.

U.M.

1 INPUT

2 INPUTS

LA

1

247

- - - -

247

247

Lb

0

3

- - - -

2

2

LP

0

2

- - - -

2

2

(1)

the unit of measurement depends on parameter P2

(2)

set the parameters relative to the regulators appropriately after modification of parameter P2

(3)

the value depends on the type of functioning (1 with 1 measurement input and 3 with 2 measurement inputs)

(4)

the value depends on the type of functioning (2 with 1 measurement input and 4 with 2 measurement inputs)

(5)

steam injection becomes available again when the temperature of the steam reaches the steam set-point again

(6)

ds = tenths of second

(7)

the top output and the floor output are switched-on alternately for half of the time established with parameter c1

(8)

the buzzer and the acoustic output are activated before the conclusion of the cooking timer count (of the time established with the parameter c9), for the time established with parameter c4

(9)

if the cooking timer is interrupted (with the procedure given in paragraph 5.4 or by activation of the malfunction input), the duration of buzzer activation and of the acoustic output and the flashing duration
of the 00:00 indication will be 3 seconds

(10)

if the economy function is in progress, any instrument switch-off will cause interruption of the function. A power cut will not cause interruption of the function but the re-start of the time count established with
parameter c10

(11)

the parameter differential is 10 °C/18 °F

(12)

pressing the key

causes the associated effect.

with 1 measurement input, type of chamber temperature alarm delay; with 2 measurement inputs, type of top temperature alarm delay
0 = no alarm
1 = absolute (i.e. A1)
2 = with 1 measurement input, relative to the work set-point (i.e. “work set-point + A1”); with 2 measurement inputs, relative to the top set-point (i.e. “top

set-point + A1”)

floor temperature above which the floor temperature alarm is activated, see also A6 (11)
floor temperature alarm delay
type of floor temperature alarm
0 = no alarm
1 = absolute (i.e. A4)
2 = relative to the floor set-point (i.e. “floor set-point + A4”)
DIGITAL INPUTS
on/stand-by input polarity
0 = live input active
1 = non-live input active
effect caused by the activation of the multifunction input
0 = no effect
1 = START/INTERRUPTION OF THE COOKING TIMER - the activation of the input will cause the cooking timer to start and the successive activation will cause

its interruption

2 = CHAMBER LIGHT SWITCH-ON/OFF - the activation of the input will cause the chamber light to switch-on and the successive activation will cause its

switch-off

3 = BUZZER, ACOUSTIC OUTPUT AND BUZZER OUTPUT DEACTIVATION - the activation of the input will cause deactivation of the buzzer, the acoustic

output and the buzzer output (activate the input again to deactivate these utilities again)

4 = STEAM INJECTION - in this case:

• if t0 = 0, the activation of the input causes the injection of steam for the time established with parameter t2 or for the entire duration that the key is

pressed (parameter t1 establishes the minimum time that can pass between the two successive injections) (12)

• if t0 = 1, the activation of the input will enable automatic steam injection (in cyclical mode; parameter t2 establishes the duration of the switch-on

of the injector and parameter t1 establishes the duration of switch-off) until the input is activated again (12)

5 = DOOR MICRO SWITCH - the activation of the input causes the deactivation of the top output and the floor output, prevents steam injection, displays

the flashing “id” code in the upper part of the display and activates the buzzer until the input is deactivated; see also i7

6 = START/STOP OF THE ECONOMY FUNCTION - activation of the input causes the activation of the economy function and successive activation will cause

interruption

type of contact of the multifunction input
0 = NO (input active with closed contact)
1 = NC (input active with open contact)
multifunction input alarm signal delay (only if i5 = 5)
SERIAL NETWORK (MODBUS)
instrument address
baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
parity
0 = none (no parity)
1 = odd
2 = even