EVCO EV9326J9 User Manual

Page 2

background image

Evco S.p.A. • Code 1049326E00 • page 2/6

- if P5 = 2, the display will show the floor temperature
- if P5 = 3, the display will show the floor set-point
• the lower part of the display will show the size established with

parameter P6:

- if P6 = 0, the display will show the top temperature
- if P6 = 1, the display will show the top set-point (in this case the “set”

LED and the “1” LED will be on).

- if P6 = 2, the display will show the value of the cooking timer or its

count if the timer is active (in this case the “timer” LED will be on); the
value of the cooking timer is displayed in the hours:minutes format

- if P6 = 3, the display will show the floor temperature
- if P6 = 4, the display will show the floor set-point (in this case the “set”

LED and the “2” LED will be on).

See also paragraphs 3.5 and 3.7.
If the instrument is in the stand-by state:
• the upper part of the display will be off
• the lower part of the display will be off
• the LED will be on.
3.4

Temporary setting of the quantity shown by the
upper part of the display during the on state

• make sure no procedure is in progress
• press

and

for 1s several times: the upper part of the display
will show one of the labels given in the tables in
paragraph 3.5 for 2 secs, after which it will show
the corresponding value.

Any power supply cut-off causes the display of the quantity estab-
lished with parameter P5 to be restored.
3.5

Learning the quantity shown by the upper part of
the display during the on state

• make sure no procedure is in progress
• press

and

: if functioning with 1 measurement input, the
upper part of the display will show one of the
labels given in the following table for 2 seconds:

LABEL MEANING

Pb

chamber temperature

SP

work set-point

PbS

steam temperature

If the steam probe is not enabled (parameter P4 = 0), the “PbS” label
will not be displayed.
if functioning with 2 measurement inputs, the upper part of the dis-
play will show one of the labels given in the following table for
2 seconds:

LABEL MEANING

Pb1

temperature of the top

SP1

top set-point

Pb2

temperature of the floor

SP2

floor set-point

3.6

Temporary setting of the quantity shown by the
lower part of the display during the on state

• make sure no procedure is in progress
• press

and

for 1s several times: the lower part of the display
will show one of the labels given in the tables in
paragraph 3.7 for 2 secs, after which it will show
the corresponding value.

Any power supply cut-off causes the display of the quantity estab-
lished with parameter P6 to be restored.
3.7

Learning the quantity shown by the lower part of
the display during the on state

• make sure no procedure is in progress
• press

and

: if functioning with 1 measurement input, the
lower part of the display will show one of the
labels given in the following table for 2 seconds:

LABEL MEANING

Pb

chamber temperature

SP

work set-point

tine

value of the cooking timer or its count if the timer is active

PbS

steam temperature

If the steam probe is not enabled (parameter P4 = 0), the “PbS” label
will not be displayed.
if functioning with 2 measurement inputs, the lower part of the dis-
play will show one of the labels given in the following table for 2
seconds:

LABEL MEANING

Pb1

temperature of the top

SP1

top set-point

tine

value of the cooking timer or its count if the timer is active

Pb2

temperature of the floor

SP2

floor set-point

3.8

Chamber light switch on/off

• make sure no procedure is in progress
• press
Using the multifunction input, it is also possible to cause the same
effect caused by pressing the key

in remote mode.

If the chamber light is not managed by any digital output, pressing the

key will cause the display of the “no” indication for 1s in the lower

part of the display.
3.9

Buzzer silencing

• make sure no procedure is in progress

• press a key (the first time the key is pressed, the associated effect is not

caused).

Pressing the key also causes the deactivation of the acoustic output

and the buzzer output.

Using the multifunction input, it is also possible to deactivate the buzzer,
the acoustic output and the buzzer output in remote mode.

4

SETTINGS

4.1

Setting the type of functioning (with 1 measure-
ment input rather than 2)

To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-

dure is in progress

• press

and

for 4s: the upper part of the display will show
“PA”

• press

: the lower part of the display will show the correspond-
ing value

• press

or

within 15s to set “743”

• press
• press

and

for 4s: the upper part of the display will show
“Pb”.

To modify the type of functioning:
• press

: the lower part of the display will show the correspond-
ing value.

The meaning of the values is the following:

VALUE MEANING

1

functioning with 1 measurement input (default, chamber
probe)

2

functioning with 2 measurement inputs (top probe and
floor probe)

• press

or

within 15s

• press
To exit the procedure:
• press

and

for 4s.

The modification of the type of functioning does not cause
the configuration parameters default value to be restored.
4.2

Setting the utility managed by the relay K3 and
the relay K6

To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-

dure is in progress

• press

and

for 4s: the upper part of the display will show
“PA”

• press

: the lower part of the display will show the correspond-
ing value

• press

or

within 15s to set “743”

• press
• press

and

for 4s: the upper part of the display will show
“Pb”

• press

or

to select “do3” or “do6”.

The label meaning is the following:

LABEL MEANING

do3

utility managed by the third digital output (relay K3)

do6

utility managed by the sixth digital output (relay K6)

To modify the utility managed by an output:
• press

: the lower part of the display will show the correspond-
ing value.

The meaning of the values is the following:

VALUE MEANING

0

not used

1

chamber light

2

steam generator

3

alarm

4

cooking timer

5

acoustics

6

on/stand-by

• press

or

within 15s

• press
To exit the procedure:
• press

and

for 4s.

4.3.1 Setting the work set-point (only if functioning with

1 measurement input)

• make sure that the instrument is in on state and that no procedure is

in progress

• press

: the lower part of the display will show “SP”, the upper
part the corresponding value and the LED

will flash

• press

or

within 15s; see also parameters r1 and r2

• press

3 times or do not operate for 15s: the LED

will switch-

off, after which the instrument will exit the procedure.

To exit the procedure in advance:

• do not operate for 15s (any modifications will be saved).
It is also possible to set the work set-point via the SP parameter.
4.3.2 Setting the top set-point and the floor set-point

(only if functioning with 2 measurement inputs)

To modify the top set-point:

• make sure that the instrument is in on state and that no procedure is

in progress

• press

: the lower part of the display will show “SP1”, the upper
part the corresponding value and the LED

will flash

• press

or

within 15s; see also parameters r1 and r2

• press

2 times or do not operate for 15s: the LED

will switch-

off, after which the instrument will exit the procedure.

To modify the floor set-point:
• press

during the modification of the top set-point: the lower
part of the display will show “SP2”, the upper part the
corresponding value and the LED

will flash

• press

or

within 15s; see also parameters r7 and r8

• press

: the LED

will switch-off, after which the instrument

will exit the procedure.

To go back to previous levels:
• press

several times during the procedure.

To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the top set-point via parameter SP1 and the floor
set-point via parameter SP2.
4.4

Setting the power distributed to the top and the
power distributed to the floor (only if functioning
with 1 measurement input)

To modify the power distributed to the top:
• press

during the modification of the work set-point: the lower
part of the display will show “Po1”, the upper part the
corresponding value and a proportioned number of bars
of the LED will flash

• press

or

within 15s; see also parameters c0 and c1

• non operare per 15 s: the LED will switch-off, after which the

instrument will exit the procedure.

To modify the power distributed to the floor:
• press

during the modification of the power distributed to the
top: the lower part of the display will show “Po2”, the
upper part the corresponding value and a proportioned
number of bars of the LED will flash

• press

or

within 15s; see also parameters c0 and c1

• press

: the LED will switch-off, after which the instrument will
exit the procedure.

To go back to previous levels:
• press

several times during the procedure.

To exit the procedure in advance:
• do not operate for 15s (any modifications will be saved).
It is also possible to set the power distributed to the top through pa-
rameter Po1 and the power distributed to the floor through param-
eter Po2.
4.5

Setting the configuration parameters

To access the procedure:
• make sure that the instrument is in stand-by state and that no proce-

dure is in progress

• press

and

for 4s: the upper part of the display will show
“PA”

• press

: the lower part of the display will show the correspond-
ing value

• press

or

within 15s to set “-19”

• press

or do not operate for 15s

• press

and

for 4s: if functioning with 1 measurement input,
the upper part of the display will show “SP”; if
functioning with 2 measurement inputs, the
upper part of the display will show “SP1”.

To select a parameter:
• press

or

To modify a parameter:
• press

: the lower part of the display will show the correspond-
ing value

• press

or

within 15s

• press

or do not operate for 15s.

To exit the procedure:
• press

and

for 4s or do not operate for 60s (any modifica-
tions will be saved).

Cut the instrument power supply off after modification of
the parameters.
4.6

Restore the default value of the configuration pa-
rameters

• make sure that the instrument is in stand-by state and that no proce-

dure is in progress

• press

and

for 4s: the upper part of the display will show
“PA”

• press

: the lower part of the display will show the correspond-
ing value

• press

or

within 15s to set “743”

• press

or do not operate for 15s

• press

and

for 4s: the upper part of the display will show
“Pb”

• press

or

to select “dEF”

• press

: the lower part of the display will show the correspond-
ing value

• press

or

within 15s to set “149”

• press

or do not operate for 15s: the upper part of the display
will show “dEF” flashing for 4s, after which “dEF” will
switch on

• cut the instrument power supply off.
To exit the procedure in advance:
• press

and

for 4s during the procedure (i.e. before setting
“149”: restore will not be carried out).

Make sure that the default value of the parameters is
appropriate.
5

COOKING TIMER

5.1

Preliminary considerations

The cooking timer allows to start the reverse count of a time.
The count is shown in the lower part of the display; during the count
the “timer” LED is on and the timer output is activated.
Before conclusion of the count (of the time established with parameter
c9) the buzzer and the acoustic output are activated, for the time estab-
lished with parameter c4.
Before conclusion of the count (of the time established with parameter
c5) the airhole is activated, for the time established with parameter c6.
Using the multifunction input, it is also possible to start/interrupt the
cooking timer in remote mode.