beautypg.com

Table 1-1. common switch settings – Comtrol API (6508) for the MS-DOS User Manual

Page 6

background image

6

Installating RocketPort/ISA Systems

Installating RocketPort/ISA Systems

Note: Press <

F1

> on any item for button-sensitive Help.

5.

Select the

I/O

address range for each RocketPort series controller.

a.

Use the<Tab> key and the <

ALT

> <Down Arrow> key combination or

<click> on the arrow next to the

I/O

Address Range box to view the

I/O

address ranges.

b.

Use an <Arrow> key or the mouse cursor to highlight the

I/O

range you

want to select.

c.

Press <Enter> or <Click> to execute the selection.

The

I/O

address identifies the location in the system’s

I/O

space used to pass

control information between the system and the controller.

For the first controller, you will select a 68-byte

I/O

address range. For

subsequent controllers, you will select a 64-byte range.

Most peripherals use

I/O

address ranges between 0 and 3FF hexadecimal.

If you have peripherals installed above 400h, you may experience an

I/O

conflict.

RocketPort controllers use

I/O

address ranges at 400h intervals above the

I/O

address range. Make sure that other peripherals in the system do not

use these

I/O

address ranges. See Table 3-1 for information about common

I/O

usage.

4.

Enter a path name for the

API

directory, if you do not want to use the

default path,

\ROCKET

.

5.

Select an interrupt (

IRQ

) for the controller that does not conflict with an

existing interrupt.

6.

Select <Ok to Install>.

7.

Select <

OK

> at the confirmation screen.

8.

Set the

DIP

switches on the controller as directed in the summary screen.

You may want to fill in the blank switches provided for you or place a check
mark in Table 1-1, which illustrates common

I/O

ranges.

Press <

ENTER

> to view the

DIP

switch settings for additional controllers.

Notes: You may want to set the

DIP

switches for the controllers while

looking at the summary screen.

You can also use the

\ROCKET\INSTALL.LOG

file to set the switches,

if you do not set them at this time.

9.

Make sure that you note the line that you must add to the

AUTOEXEC.BAT

file. For example:

SET ROCKETCFG=C:\ROCKET\CONFIG.DAT

This path is the same path where the

API

is installed.

Note: After you create your own applications, you may need to change the

configuration file (see Subsection 2.3).

10. When your cursor returns to the

DOS

prompt, remove the diskette from the

drive.

11. Edit the

AUTOEXEC.BAT

file as directed in Step 9.

Go to the next subsection to install the controller.

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

Controller #1

Controller #2

Controller #3

Controller #4

Table 1-1. Common Switch Settings

Controller

#1

I/O

Address

Range

DIP

Switch Settings

Controller #1 determines other

controller settings

100 - 143 hex

140 - 183 hex

180 - 1C3 hex
(Default)

1st ISA

2nd ISA

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

3rd ISA

4th ISA

1st ISA

2nd ISA

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

3rd ISA

4th ISA

1st ISA

2nd ISA

ON

1

2

3

4

5

6

7

8

ON

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

3rd ISA

4th ISA