beautypg.com

Step3, Electrical connections, Ground fault circuit interrupters – Kenmore 362.7562 User Manual

Page 42: Caution, Installation instructions (continued)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

INSTALLATION INSTRUCTIONS (continued)

1. Instali a manual gas line shut-off valve in the gas line

in an easily accessed location outside of the range.

Make sure everyone operating the range knows where

and how to shut off the gas supply to the range.

2. Install male Vs" flare union adapter to the Vz" NPT

internal thread elbow at inlet of pressure regulator.

Use a back-up wrench on the regulator fitting to avoid

damage.

When installing the range from the front, remove the 90°

elbow for easier installation.

3. Install male Va" or %" flare union adapter to the NPT

internal thread of the manual shut-off valve, taking care
to back up the shut-off valve to keep it from turning,

4. Connect flexible metal appliance connector to the

adapter on the range. Position range to permit
connection at the shut-off valve.

5. When all connections have been made, make sure all

range controls are in the off position and turn on the
main gas supply valve. Use a liquid leak detector at all

joints and connections to check for leaks in the system,

CAUTION

: DO NOT USE A FLAME TO

CHECK FOR GAS LEAKS.

When using test pressures greater than 'h psig to
pressure test the gas supply system of the residence,
disconnect the range and individual shut-off valve from
the gas supply piping. When using test pressures of Vz
psig or less to test the gas supply system, simply isolate
the range from the gas supply system by closing the

individual shut-off valve.

STEP3
Electrical Connections

{on some models)

Electrical Requirements

120-voIt, 60 Hertz, properly grounded branch circuit

protected by a 15-amp or 20-amp circuit breaker or time
delay fuse.

Extension Cord Cautions

Because of potential safety hazards associated with
certain conditions, we strongly recommend against the
use of an extension cord. However, if you still elect to use
an extension cord, it is absolutely necessary that it be a

UL-listed, 3-wire grounding-type appliance extension cord

and that the current carrying rating of the cord in
amperes be equivalent to, or greater than, the branch
circuit rating.

Grounding—IMPORTANT (Please read carefully)

FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE
PROPERLY GROUNDED.

PREFERRED

METHOD

Ensure proper

ground exists

before use

The power cord of this
appliance is equipped
with a three-prong

(grounding) piug which
mates with a standard

three-prong grounding
wall receptacle to

minimize the possibility

of electric shock hazard
from this appliance.

The customer should have the wall receptacle and
circuit checked by a qualified electrician to make sure
the receptacle is property grounded,,

Where a standard two-prong wall receptacle is
encountered, it is the personal responsibility and
obligation of the customer to have it replaced with
a properly grounded three-prong wall receptacle.

DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR
REMOVE THE THIRD (GROUND) PRONG FROM THE

POWER CORD.

Ground Fault Circuit Interrupters

Ground Fault Circuit Interrupters (GFCIs) are devices
that sense leakage of current in a circuit and automatically

switch off power when a threshold leakage level is

detected. These devices must be manually reset by
the consumer.

Although the National Electrical Code requires the use of
GFCIs in kitchen receptacles installed to serve countertop
appliances, GFCIs are not required or recommended in a
receptacle serving a gas range.

Performance of the range wilt not be affected

if operated on a GFCI-protected circuit, but occasional

nuisance tripping of the GFCI breaker is possible,
if the breaker trips, power to the range will switch off.

42

This manual is related to the following products: