Testing the Thermostat

5

WARNING!

Read BEFORE Testing

• Do not short (or jumper) across terminals on the gas valve or at the heating

or cooling system control board to test the thermostat installation. This

could damage the thermostat and void the warranty.
• Do not select COOLING test modes if the outside temperature is below
50° F (10° C). Doing so could possibly damage the compressor system and

may cause personal injury.
• This thermostat includes an automatic compressor protection feature

that is DISABLED during test mode. When testing, DO NOT quickly switch

the compressor on, off and on. Doing so could possible damage the

compressor and may cause personal injury.

This thermostat features a menu driven operational test mode. This test
mode is intended for use by trained HVAC technicians. If you are unfamiliar
with the operation of this equipment, please contact a qualified service
technician to perform these tests.

• To START TEST MODE, Press

PROG and at the same time for 3 seconds.

• To NAVIGATE TEST MODE, Press

RETURN to move forward to the next test type.

• TO RUN THE TEST, press to start or stop the test.
• To EXIT TEST MODE, Press

PROG and RETURN at the same time for 3 seconds.

Test Type

System Function

System Type

Active Terminals

Cooling

1st Cooling Stage

Conventional

Y1, O, G

or Heat Pump

Cooling

2nd Cooling Stage

Conventional

Y1, Y2, O, G

or Heat Pump

Heating

1st Heating Stage

Conventional

W1, B, G*

Heating

1st Heating Stage

Heat Pump

Y1, B, G

Heating

2nd Heating Stage

Conventional

W1, W2, B, G*

Heating

2nd Heating Stage

2 Stage

Y1, W2, B, G

Heat Pump

Heating

2nd Heating Stage

3 Stage

Y1, Y2, B, G

Heat Pump

Heating

3rd Heating Stage

3 Stage

Y1, Y2, W3, B, G

Heat Pump

Heating

Emergency Heat

2 or 3 Stage

E, B, G*

Heat Pump

Fan

Fan Only

Conventional

G

or Heat Pump

To provide time to verify equipment operation, a test will run for 5 minutes.
At the end of that time, the thermostat will return to normal operating mode.
To stop a test early press

PROG and RETURN at the same time for 3 seconds.

NOTE: Only tests that apply to the current thermostat settings will be

displayed. As an example, tests for 3rd stage heating will not be available on

a thermostat configured for a 2 stage conventional system.
*Notes on Fan (G Terminal) Function: The G terminal will only be active if the
stages are configured as electric heat. Systems that have the heating stages
configured as gas will not activate the fan (G) terminal.