Testing the Thermostat
5
WARNING!
Read BEFORE Testing
• Do not short (or jumper) across terminals on the gas valve or at the heating
or cooling system control board to test the thermostat installation. This
could damage the thermostat and void the warranty.
• Do not select COOLING test modes if the outside temperature is below
50° F (10° C). Doing so could possibly damage the compressor system and
may cause personal injury.
• This thermostat includes an automatic compressor protection feature
that is DISABLED during test mode. When testing, DO NOT quickly switch
the compressor on, off and on. Doing so could possible damage the
compressor and may cause personal injury.
This thermostat features a menu driven operational test mode. This test
mode is intended for use by trained HVAC technicians. If you are unfamiliar
with the operation of this equipment, please contact a qualified service
technician to perform these tests.
• To START TEST MODE, Press
PROG and at the same time for 3 seconds.
• To NAVIGATE TEST MODE, Press
RETURN to move forward to the next test type.
• TO RUN THE TEST, press to start or stop the test.
• To EXIT TEST MODE, Press
PROG and RETURN at the same time for 3 seconds.
Test Type
System Function
System Type
Active Terminals
Cooling
1st Cooling Stage
Conventional
Y1, O, G
or Heat Pump
Cooling
2nd Cooling Stage
Conventional
Y1, Y2, O, G
or Heat Pump
Heating
1st Heating Stage
Conventional
W1, B, G*
Heating
1st Heating Stage
Heat Pump
Y1, B, G
Heating
2nd Heating Stage
Conventional
W1, W2, B, G*
Heating
2nd Heating Stage
2 Stage
Y1, W2, B, G
Heat Pump
Heating
2nd Heating Stage
3 Stage
Y1, Y2, B, G
Heat Pump
Heating
3rd Heating Stage
3 Stage
Y1, Y2, W3, B, G
Heat Pump
Heating
Emergency Heat
2 or 3 Stage
E, B, G*
Heat Pump
Fan
Fan Only
Conventional
G
or Heat Pump
To provide time to verify equipment operation, a test will run for 5 minutes.
At the end of that time, the thermostat will return to normal operating mode.
To stop a test early press
PROG and RETURN at the same time for 3 seconds.
NOTE: Only tests that apply to the current thermostat settings will be
displayed. As an example, tests for 3rd stage heating will not be available on
a thermostat configured for a 2 stage conventional system.
*Notes on Fan (G Terminal) Function: The G terminal will only be active if the
stages are configured as electric heat. Systems that have the heating stages
configured as gas will not activate the fan (G) terminal.
Econ
Economizer
Business