Programming Installer Settings

4

Setting Thermostat Installer Options

The Installer Options section allows the system and programming parameters
to be set up at installation. The Installer Options mode is menu driven. As the
different options are programmed you may eliminate specific options. For
example, if the system is set to single stage heat pump, Option 8, selecting
the AUX stage fan control will no longer be available.

The Installer Option mode is entered by holding the

RETURN and buttons

together for 3 seconds. Installer Option 1 (Residential or Commercial) will be
displayed. Pressing the or buttons will scroll between choices. To scroll to
the next installer option, press the

RETURN button. To scroll backwards between

installer options, press the

PROG button. The thermostat will return to normal

operating mode by pressing the

RETURN and PROG buttons at the same time.

NOTE: The thermostat will return to normal operating mode automatically after

30 seconds if no buttons are pressed.

NOTE: Any changes to Installer Option 6 (System Type) will cause Options 7, 8, 9,

10 and 11 to reset to the default values that are dependent on system selection.

NOTE: Any changes to Installer Options 1 through 6 will cause all User Options

and Programming to reset to their default values if the User Options were

previously programmed. See User Manual, Section 2.

cont.

Programming Installer Settings

4

Setting Thermostat Installer Options

(continued)

Only available in Business Mode.
Selects Outside Air Intake Options
of None (disabled), Economizer
Mode and Time of Day Mode.

Only available if auto changeover is
enabled in option 5. Selects Auto
Changeover Dead Band of 2, 3, 4,
5˚ F (1.0, 1.5, 2.0, 2.5˚ C).

IMPORTANT:

At installation, Remote

Indoor Sensor must be

at room temperature.

Only available if remote sensor is
installed. Selects between Internal
(I), External (E) and Averaging (A)
control of internal (thermostat) and
external (remote indoor sensor) for
termperature control. Attaching an
outdoor sensor for outdoor
temperature display or balance
point control is automatically
detected. Test outdoor sensor
connection by pressing PROG and
HOLD at the same time.