beautypg.com

5300_install_10_11.pdf, Programming installer settings – Braeburn 5300 3H-2C Installer Manual User Manual

Page 6

background image

10

11

cont.

Programming Installer Settings

4

Option Setting

Temperature

Control

sens I (Internal

At Thermostat

N/A

Thermostat Sensor)

sens E (External

At Remote Sensor

N/A

Remote Indoor Sensor)

sens A (Internal

Average between

N/A

and Remote)

Internal and Remote

Balance Points and
Outdoor Display

17. The keypad lockout feature has two levels of security. Level one locks all

buttons (including the reset) except for the , and backlight buttons. Level

2 locks the entire keypad except the backlight button. The and buttons

can be pressed together to enter the lock code but the buttons do not work

individually to adjust the temperature. The lock level is set during the Installer

Options and the lock code is set in the User Options. See the User Manual,

Section 2.

18. When Auto Changeover mode is enabled and selected, the system automatically

switches between heating and cooling when the room temperature meets the

normal criteria for either a heating or cooling call. There is a forced separation

(dead band) between the heating and cooling set points, so the systems do not

work against each other. This option selects Auto Changeover Dead Band of 2º,

3º, 4º or 5º F. The default is 3º F.

19. Only available with multi-stage heat pump and outdoor sensor connected.

Locks out the use of the compressor heat stage for outside air temperatures

less than installer setting. Select from no lockout or a setting between 10º F to

50º F (-9º C to 10º C).

cont.

Programming Installer Settings

4

Time Step / Override

Cooling Call

Occupied

YES or NO

ON

ON

OFF

Unoccupied

YES

ON

OFF

OFF

NO

OFF

OFF

OFF

Override

YES or NO

ON

ON

OFF

External Air Output (A)
Economizer Time of Disabled
Mode

Day Mode

16. If a Braeburn

®

indoor or outdoor remote sensor is connected during installation,

the thermostat will automatically detect the type of sensor. When an indoor

sensor is detected, you may select between internal (sensI), external (sensE),

or averaging (sensA) for temperature control. When an outdoor sensor is

automatically detected, the thermostat will remove the choices for indoor

sensing from the menu and enable outdoor measurement. The outdoor sensor

may be used to determine if balance points have been exceeded, and outdoor

temperature display. For proper auto-detection, you must use a Braeburn brand

external sensor. Should the external sensor become unwired, the thermostat

will retain the settings, but the balance points, and outdoor temperature display

will be disabled until the external sensor is repaired. Test the operation of the

external sensor by pressing the

PROG and HOLD buttons at the same time.

20. Only available with multi-stage heat pump and outdoor sensor connected.

Locks out the use of the auxiliary heat stage for outside air temperatures over

installer setting. Select from no lockout or a setting between 70º F to 40º F

(21º C to 4º C).

NOTE: This balance point overrides the fossil fuel compressor

lockout. If the lockout is set to AG and the outdoor temperature is over the AUX

balance point, the compressor will remain on during a second stage call. The

unit will recover to the set point without the AUX stage.
21. Selects Outside Air Intake Options. Scroll between none (disabled), economizer

mode and time of day mode. Enables the operation of an outside air damper

system in either the economizer mode or time of day mode. Available only in

commercial (BUS) mode.

22. Selects the heating set point upper limit, scrolls between 90º F and 60º F

(32º C and 10º C).

23. Selects the cooling set point lower limit, scrolls between 45º F and 80º F

(7º C and 27º C).

Time Step / Override

Heating Call

Occupied

YES or NO

ON

ON

OFF

Unoccupied

YES

OFF

OFF

OFF

NO

OFF

OFF

OFF

Override

YES or NO

ON

ON

OFF

External Air Output (A)
Economizer Time of Disabled
Mode

Day Mode