Introduction – AERCO ECS Retrofit User Manual
Page 74

74
INTRODUCTION
The information included in this Appendix lists optional items which may vary, depending on:
• Type of Water Heater being retrofitted
• Required Water Heater flow rate
• Type of Control Valve Actuator previously installed
• Control Valve size
Table B-1 and the Tables/Appendices referenced therein, list the applicable items included in the 
Retrofit Kit for the specific Water Heater being retrofitted. 
 
TABLE B-1. ECS RETROFIT KIT OPTIONAL ITEMS
ITEM
DESCRIPTION
LOCATION ON UNIT
QTY.
REFERENCE
TABLE/APPENDIX
1
Orifice Disc
Cold Water Inlet
1
Table B-2
2
Compound Pressure Gauge 
(Steam-to Water Units ONLY) 
Steam Inlet to Heater
1
Table B-3
3
Valve Flange Gaskets 
(2.50” to 4.00” Valves ONLY) 
Control Valve Inlet & 
Outlet Flanges 
2 Table
B-4
4
Pneumatic or Electro-Hydraulic 
Actuator Replacement Kit 
Control Valve
1
Appendix C
5 Self-Contained
Actuator
Replacement Kit
Control Valve
1
Appendix D
TABLE B-2. ORIFICE DISC OPTIONS (Table B-1, Item 1)
AERCO
PART NO.
QTY
WATER HEATER
FLOW RATE (GPM)
APPLICABLE UNITS
49032-1
1
0 – 45
B-Plus, B-Plus II, E-Plus
49032-2
1
0 – 70
B-Plus, B-Plus II, E-Plus
49032-3
1
0 – 125
B-Plus, B-Plus II, E-Plus
49032-4
1
> 125
B-Plus, B-Plus II, E-Plus
49032-5
1
0 – 45
A-Plus, DW-24
49032-6
1
0 – 70
A-Plus
49032-7
1
0 – 100
DW-45, DW-68
49032-8
1
0 – 45
DW-45, DW-68
49032-9
1
0 – 125
DW-45, DW-68
49032-10 1
>
125
DW-68
 
 