3. Press down on the Linkage Adapter and verify that the Indicator Plate is aligned with the “0”

Scale marking.

4. With the Indicator Plate properly aligned, tighten the U-bolt hex nuts using an 8 mm wrench.

Torque the nuts to 60 in-lbs.

5. This completes the mechanical installation of the Actuator Assembly. The electrical

connections will be made during installation of the Control Box in paragraph 4.7.


90

Figure 4-4. Actuator Assembly, Part No. 69009