Extracted Information From 248 CMR 5.08 (2) – Continued
a. In the event that the side wall horizontally vented gas fueled equipment is installed in 
a crawl space or an attic, the hard wired carbon monoxide detector with alarm and 
battery back-up may be installed on the next adjacent floor level. 
b. In the event that the requirements of this subdivision can not be met at the time of 
completion of installation, the owner shall have a period of thirty (30) days to comply with 
the above requirements; provided, however, that during said thirty (30) day period, a 
battery operated carbon monoxide detector with an alarm shall be installed. 
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as 
required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 
2034 listed and IAS certified. 
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior 
of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust 
vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign 
shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. 
KEEP CLEAR OF ALL OBSTRUCTIONS". 
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled 
equipment shall not approve the installation unless, upon inspection, the inspector observes 
carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 
5.08(2)(a)1 through 4. 
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the 
most current edition of NFPA 54 as adopted by the Board; and 
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or 
structure separate from the dwelling, building or structure used in whole or in part for residential 
purposes. 
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When 
the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting 
system design or venting system components with the equipment, the instructions provided by the 
manufacturer for installation of the equipment and the venting system shall include: 
1. Detailed instructions for the installation of the venting system design or the venting system 
components; and 
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. 
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does 
not provide the parts for venting the flue gases, but identifies "special venting systems", the following 
requirements shall be satisfied by the manufacturer: 
1. The identification of each "special venting system" shall include the listing of either the 
website, phone number or manufacturer’s address where the venting system installation 
instructions can be obtained; and 
2. The "special venting systems" shall be Product Approved by the Board, and the instructions 
provided with the system shall include a parts list and detailed installation instructions. 
(e) A copy of all installation instructions for the Product Approved side wall horizontally vented gas fueled 
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design 
instructions shall remain with the appliance or equipment at the completion of the installation. 
 
_________________________________
[End of Extracted Information From 248 CMR 5.08 (2)]
 
 