beautypg.com

Installation, operation & maintenance, 10 table 2-1. modulex data plate entries – AERCO Modulex General Manual User Manual

Page 26

background image

INSTALLATION, OPERATION & MAINTENANCE

2-10



Table 2-1. Modulex Data Plate Entries


MODEL

NUMBER

MLX-303 MLX-454 MLX-606 MLX-757 MLX-909 MLX-1060

REVISION

A A A A A A

TYPE OF GAS

NATURAL GAS

(MLX-303B)

OR PROPANE

(MLX-303BP)

NATURAL GAS

(MLX-454B)

OR PROPANE

(MLX-454BP)

NATURAL GAS

(MLX-606B)

OR PROPANE

(MLX-606BP)

NATURAL GAS

(MLX-757B)

OR PROPANE

(MLX-757BP)

NATURAL GAS

(MLX-909B)

OR PROPANE

(MLX-909BP)

NATURAL GAS

(MLX-1060B

OR PROPANE

(MLX-1060BP)

*SERIAL NO.

303-XX-XXXX 454-XX-XXX 606-XX-XXXX 757-XX-XXXX 909-XX-XXXX 1060-XX-

XXXX

MAX INPUT

303,000 454,000 606,000 757,000 909,000 1,060,000

MIN INPUT

45,000 45,000 45,000 45,000 45,000 45,000

OUTPUT

279,000 418,000 558,000 696,000 835,000 975,000

NET IBR RATING

237,000 355,000 474,000 592,000 710,000 829,000

BOILER CATEGORY

IV IV IV IV IV IV

MAX INLET (SUPPLY)
GAS PRESSURE

14” W.C

(34.8 mbar).

14” W.C

(34.8 mbar).

14” W.C

(34.8 mbar).

14” W.C

(34.8 mbar).

14” W.C

(34.8 mbar).

14” W.C

(34.8 mbar).

MIN INLET (SUPPLY)
GAS PRESSURE

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

*NORMAL MANIFOLD
GAS PRESSURE

3.2” Nat. Gas

(MLX-303B)

2.5” Propane

(MLX-303BP)

3.2” Nat. Gas

(MLX-454B)

2.5” Propane

(MLX-454BP)

3.2” Nat. Gas

(MLX-606B)

2.5” Propane

(MLX-606BP)

3.2” Nat. Gas

(MLX-757B)

2.5” Propane

(MLX-757BP)

3.2” Nat. Gas

(MLX-909B)

2.5” Propane

(MLX-909BP)

3.2” Nat. Gas
(MLX-1060B)

2.5” Propane

(MLX-1060BP)

OPTIMAL INLET
(SUPPLY) GAS
PRESSURE

7.0”

(17.4 mbar)

7.0”

(17.4 mbar)

7.0”

(17.4 mbar)

7.0”

(17.4 mbar)

7.0”

(17.4 mbar)

7.0”

(17.4 mbar)

* NOTE: Normal manifold gas pressure measured at downstream port of gas valve ((Figure 6-2).