beautypg.com

Installation, operation & maintenance – AERCO Modulex General Manual User Manual

Page 13

background image

INSTALLATION, OPERATION & MAINTENANCE

1-5

1.5 - TECHNICAL DATA

(THE NAME PLATE IS PLACED UNDER THE FRONT JACKET NEXT TO THE

CONTROL PANEL.)

Model Number

Min Input

Max Input

Max Output*

Net IBR Rating

MLX-303

45,500 303,000 260,000-279,000 237,000

MLX-454

45,500 454,000 390,000-418,000 355,000

MLX-606

45,500 606,000 521,000-558,000 474,000

MLX-757

45,500 757,000 651,000-696,000 592,000

MLX-909

45,500 909,000 781,000-835,000 710,000

MLX-1060

45,500 1,060,000 912,000-975,000

829,000

DIMENSIONS:

Model Number

Height

Width

Depth

Weight

MLX-303

42” (1067 mm)

28” (711 mm)

27” (686 mm)

331 lbs. (150.1 kg)

MLX-454

42” (1067 mm)

28” (711 mm

27” (686 mm)

408 lbs. (185.1 kg)

MLX-606

42” (1067 mm)

33” (838 mm)

27” (686 mm)

496 lbs. (225.0 kg)

MLX-757

42” (1067 mm)

38” (965 mm)

27” (686 mm)

573 lbs. (259.9 kg)

MLX-909

42” (1067 mm)

44” (112 mm)

27” (686 mm)

672 lbs. (304.8 kg)

MLX-1060

42” (1067 mm)

49” (1245 mm)

27” (686 mm)

761 lbs. (345.2 kg)

SPECIFICATIONS:

Model

Number

MLX-303 MLX-454 MLX-606 MLX-757 MLX-909 MLX-1060

Boiler

Category

IV IV IV IV IV IV

Type of Gas

Natural Gas
(MLX-303B)

or Propane

(MLX-303BP)

Natural Gas
(MLX-454B)

or Propane

(MLX-454BP)

Natural Gas
(MLX-606B)

or Propane

(MLX-606BP)

Natural Gas
(MLX-757B)

or Propane

(MLX-757BP)

Natural Gas
(MLX-909B)

or Propane

(MLX-909BP)

Natural Gas

(MLX-1060B)

or Propane

(MLX-1060BP)

Gas Connections (NPT)

1.5”

1.5”

1.5”

1.5”

1.5”

1.5”

Max. Gas Pressure

14” W.C.

(34.8 mbar)

14” W.C.

(34.8 mbar)

14” W.C.

(34.8 mbar)

14” W.C.

(34.8 mbar)

14” W.C.

(34.8 mbar)

14” W.C.

(34.8 mbar)

Optimal Gas Pressure

7” W.C.

(17.4 mbar)

7” W.C.

(17.4 mbar)

7” W.C.

(17.4 mbar)

7” W.C.

(17.4 mbar)

7” W.C.

(17.4 mbar)

7” W.C.

(17.4 mbar)

Min. Gas Pressure

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

4”

(10 mbar)

Max. Allowed Working
Pressure

50 psi

(344.7 kPa)

50 psi

(344.7 kPa)

50 psi

(344.7 kPa)

50 psi

(344.7 kPa)

50 psi

(344.7 kPa)

50 psi

(344.7 kPa)

Electrical Req:

120V 15 Amp. Max.

1.2 FLA

1.8 FLA

2.4 FLA

3.0 FLA

3.6 FLA

4.2 FLA

Water Connections
(NPT)

2” 2” 2” 2” 2” 2”

Min. Water Flow (GPM)

11

17

22

28

38

39

Max. Water Flow (GPM)

28

42

55

70

84

98

Water Pressure Drop
@ Max. Flow (Ft. of
Head)

10.5 10.6 11.6 12.6 13.7 16.1