beautypg.com

Maintenance – AERCO KC1000 Low NOx Boiler equipped with C-More version 3.04 User Manual

Page 57

background image

MAINTENANCE

7. Loosen the 1/4” NPT union on the low NOx

staged ignition assembly (Figure 7.3).

8. Disconnect the staged ignition assembly 1/8”

elbow from the 3” long NPT nipple at the
bottom of the burner shell.

Figure 7.3

Burner Disassembly Diagram


9. Remove the 3” long NPT nipple and 1/4”

O.D. tube (Figure 7.3) from the burner shell.


10. Using a 7/16” socket or open end wrench,

remove the four 1/4-20 nuts on the gas inlet
pipe flange at the burner.


11. Using two 9/16” wrenches, remove the two

3/8-16 hex nuts and bolts on the gas inlet
pipe flange at the air/fuel valve (Figure 7.3).
Remove the gas inlet pipe.


12. Loosen the hose clamp on the air/fuel valve

outlet (Figure 7.3).


13. Using a 1/2” socket wrench, remove the six

5/16-18 hex nuts supporting the burner
(Figure 7.3).

14. Lower the burner while sliding the air hose

off the air/fuel valve. Remove the burner
through the rear of the unit. Due to space
limitations, it will be necessary to separate
the burner head and shell during the removal
process.


15. Disconnect the exhaust temperature sensor

by unscrewing it from the exhaust manifold
(Figure 7.4).

Figure 7.4

Exhaust Sensor Connector Location


16. Disconnect the air/fuel valve 12-pin con-

nector from the KC wiring harness.

17. Disconnect wires #24 and #17 from the

blower proof switch (Figure 7.5).


Figure 7.5

Blower Proof Switch Wire Locations

18. Loosen the hose clamp on the air/fuel valve

inlet and slide the clamp back towards the
blower (Figure 7.6).

Figure 7.6

Air/Fuel Valve Inlet Hose Clamp

7-3