CONTROL PANEL OPERATING PROCEDURES

3-2

Table 3-1. Operating Controls, Indicators and Displays

ITEM

NO.

CONTROL, INDICATOR

OR DISPLAY

FUNCTION

1

Four Status LEDs indicate the current operating status as
follows:

LED Status Indicators

COMM

Lights when RS-232 communication is occurring

MANUAL

Lights when the unit is being controlled using the front panel
keypad.

REMOTE

Lights when the unit is being controlled by an external signal
from an Energy Management System

DEMAND

Lights when there is a demand for heat.

2

VFD Display

Vacuum Fluorescent Display (VFD) consists of 2 lines, each
capable of displaying up to 16 alphanumeric characters. The
information displayed includes:

Startup Messages

Alarm Messages

Operating Status Messages

Menu Selection

3

OUTLET
TEMPERATURE

Display

3–Digit, 7–Segment LED display continuously displays the
outlet water temperature. The °F or °C LED next to the
display lights to indicate whether the displayed temperature is
in degrees Fahrenheit or degrees Celsius.

4

RS-232 Port

Port permits a Laptop Computer or External Modem to be
connected to the boiler Control Panel.

5

READY Indicator

Lights when all Pre-Purge conditions have been satisified.

6

ON/OFF Switch

Enables and disables boiler operation.

7

LOW WATER LEVEL

TEST/RESET Switches

Allow the operator to test the operation of the water level
monitor.

Pressing TEST opens the water level probe circuit and
simulates a Low Water Level alarm.

Pressing RESET resets the water level monitor circuit.
Pressing CLEAR resets the display.

8

FAULT Indicator

Red FAULT LED indicator lights when a boiler alarm
condition occurs. An alarm message will appear in the VFD.

9

CLEAR Key

Turns off the FAULT indicator and clears trhe alarm message
if the alarm is no longer valid. Lockout type alarms will be
latched and cannot be cleared by simply pressing this key.
Troubleshooting may be required to clear these types of
alarms

10

Consists of 6 keys which provide the following functions for
the Control Panel Menus:

MENU Keypad

MENU

Steps through the main menu categories shown in Figure 3-2.
The Menu categories wrap around in the order shown.

BACK

Allows you to go back to the previous menu level without
changing any information. Continuously pressing this key will
bring you back to the default status display in the VFD. Also,
this key allows you to go back to the top of a main menu
category.