AERCO KC1000 Boiler equipped with C-More 2002 User Manual
Kc series gas fired boiler system, Installation, operation & maintenance instructions, Gf-109

Printed in U.S.A.
REVISED, OCTOBER, 2010
Instruction
No.
AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA
Installation, Operation
& Maintenance Instructions
KC Series
Gas Fired
Boiler System
Semi
-Instantaneous, Condensing,
Forced Draft,
Natural Gas and Propane Fired,
Hot Water Boiler
1,000,000 BTU/HR Input
Applicable to Serial Numbers G-02-536 and above
Patent No. 4,852,524
GF-109
Table of contents
Document Outline
- KC-B-Cover-OCT-09
- Telephone Support
- Direct to AERCO Technical Support
- KC-B-TOC-11-10-08.GR
- FOREWARD A
- SECTION 1 – SAFETY PRECAUTIONS 1-1
- SECTION 2 – INSTALLATION PROCEDURES 2-1
- SECTION 3 – CONTROL PANEL OPERATING PROCEDURES 3-1
- SECTION 4 – INITIAL START-UP 4-1
- Section 5 – MODE OF OPERATION 5-1
- SECTION 6 – SAFETY DEVICE TESTING PROCEDURES 6-1
- SECTION 7 – MAINTENANCE 7-1
- SECTION 8 – TROUBLESHOOTING 8-1
- APPENDICES
- WARRANTIES W-1
- KC-B-Foreword-10-2-06-J
- KC-B-CH1-2-27-07
- KC-B-Ch2-11-25-08.GR
- Figure 2.1. Boiler Clearances
- Figure 2.2
- Figure 2.3
- Figure 2.4
- Figure 2.5a
- Figure 2.5b
- Figure 2.6
- Figure 2.7
- Figure 2.8
- Figure 2.10
- 2.6.1 CONSTANT SETPOINT MODE
- BOILER MANAGEMENT SYSTEM (BMS) MODE
- 2.6.4 REMOTE SETPOINT and DIRECT DRIVE MODES
- 2.6.5 COMBINATION MODE
- 2.7 I/O BOX CONNECTIONS
- 2.8 AUXILIARY RELAY CONTACTS
- KC-B-Ch3-11.25.08.GR
- KC-B-Ch3-11-11-09
- KC-B-Ch4-2-5-07
- KC-B-Ch4-GF109--10-09-09-dsg-bb
- KC-B-Ch5-GF109--10-05-09-dsg-bb
- KC-B-Ch6-3-5-07
- KC-B-Ch7-GF109--10-05-09-dsg-bb
- KC-B-Ch8_09-29-10
- 8.1 INTRODUCTION
- 1. Measure the actual exhaust temperature and continuity of the exhaust sensor. If the exhaust temperature is less than 475 o F and the exhaust sensor shows continuity replace the sensor.
- 2. If exhaust temperature is greater than 500 o F, check combustion calibration. Calibrate or repair as necessary.
- 2. If there are two external wires on these terminals check any Energy Management system to see if they have the units disabled (a jumper may be temporarily installed to see if the interlock circuit is functioning).
- 3. Check that proving switch for any device hooked to the interlock circuit is closing and that the device is operational.