Figure 2.8, Ac power box location, Ac power wiring diagram – AERCO KC1000 Boiler equipped with C-More 2002 User Manual
Page 16: Figure 2.10, Input/output (i/o) box location, Installation

INSTALLATION
2-6
connection to the unit are made at the Power 
Box.This box is located on the front right side of 
the unit as shown in Figure 2.8. Conduit should 
be run from the knockouts in the side of the box 
in such a manner that it does not interfere with 
the removal of any sheet metal covers. A flexible 
electrical connection may be utilized to allow the 
covers to be easily removed. 
 
POWER BOX
BLOWER
SSOV
ACTUATOR
FRAME
Figure 2.8
AC Power Box Location
NOTE:
All electrical conduit and hardware should 
be installed so that it does not interfere with 
the removal of any cover, inhibit service or 
maintenance, or prevent access between 
the unit and walls or another unit. 
2.5.1 ELECTRICAL REQUIREMENTS
Electrical requirements for each unit are 120 
VAC, 1 Phase, 60 Hz, 20 Amps from a 
dedicated electrical circuit. No other devices 
should be on the same electrical circuit as a 
KC1000 unit. A means for disconnecting AC 
power from the unit (such as a service switch) 
must be installed near the unit for normal opera-
tion and maintenance. All electrical connections 
should be made in accordance with the National 
Electrical Code and/or with any applicable local 
codes. 
 
The AC power wiring diagram is shown in Figure 
2.9. 
USE COPPER CONDUCTORS ONLY FOR FIELD WIRING
60 HZ
DISCONNECT POWER BEFORE SERVICING
DANGER: HIGH VOLTAGE
20 AMP
120 VAC,
NEUTRAL
GROUND
LINE
POWER BOX
AERCO INTERNATIONAL INC.
INPUT POWER
Figure 2.9
AC Power Wiring Diagram
2.6 MODE OF OPERATION and FIELD 
CONTROL WIRING
The KC Boiler is available in several different 
modes of operation. While each unit is factory 
configured and wired for the mode specified on 
the equipment order, some field wiring may be 
required to complete the installation. This wiring 
is typically routed to the Input/Output (I/O) Box 
located on the left side of the unit beneath the 
removable side panel (see Fig. 2.10). Field 
wiring for each particular mode of operation is 
described in the following paragraphs. For 
additional information concerning modes of 
operations, refer to Section 5. 
 
I/O
BOX
GAS SHUT-OFF VALVE
BLOWER
Figure 2.10
Input/Output (I/O) Box Location
