Chapter 6 - safety device testing, Safety device testing, Chapter 6 safety device testing – AERCO BMK 1.5 LN Dual Fuel June 2010 User Manual
Page 49: 1 testing of safety devices, Warning, Figure 6-1 low & high gas pressure testing
SAFETY DEVICE TESTING
CHAPTER 6 SAFETY DEVICE TESTING
6.1 TESTING OF SAFETY DEVICES
Periodic safety device testing is required to
ensure that the control system and safety
devices are operating properly. The Benchmark
1.5 Dual-Fuel control system comprehensively
monitors all combustion-related safety devices
before, during and after the start sequence. The
following tests check to ensure that the system
is operating as designed.
Operating controls and safety devices should be
tested on a regular basis or following service or
replacement. All testing must conform to local
codes such as ASME CSD-1.
NOTE
MANUAL and AUTO modes of operation
are required to perform the following
tests. For a complete explanation of these
modes, see Chapter 3.
NOTE
It will be necessary to remove the front
door and side panels from the unit to
perform the following tests.
WARNING
ELECTRICAL VOLTAGES IN THIS
SYSTEM MAY INCLUDE 120 AND 24
VOLTS AC. POWER MUST BE RE-
MOVED PRIOR TO PERFORMING
WIRE REMOVAL OR OTHER TEST
PROCEDURES THAT CAN RESULT
IN ELECTRICAL SHOCK.
6.2 NATURAL GAS LOW GAS
PRESSURE FAULT TEST
Refer to Figure 6-1 and ensure that the leak
detection ball valve, located below the high gas
pressure switches, is closed.
1. Ensure that the Fuel Selector Switch (Figure
4-3) is set to the NATURAL GAS position.
2. Remove the 1/8“ plug from the ball valve at
the natural gas low gas pressure switch
shown near the lower-center portion of
Figure 6-1.
3. Install a 0 – 16 “ W.C. manometer or a W.C.
gauge where the 1/8" plug was removed.
4. Slowly open the ball valve near the natural
gas low gas pressure switch.
5. Place the unit in Manual Mode and adjust
the valve position between 25 and 30%.
6. While the unit is firing, slowly close the
external manual gas shut-off valve.
7. The unit should shut down and display a
LOW GAS PRESSURE
fault message at
approximately 1.0” W.C. The FAULT indi-
cator should also start flashing.
8. Fully open the external manual gas shut-off
valve and press the CLEAR button on the
Control Box.
9. The fault message should clear and the
FAULT
indicator should go off. The unit
should restart.
10. Upon test completion, close the ball valve
and remove the manometer. Replace the
1/8 “ plug removed in step 2.
1-1/2"
SHUTOFF
VALVE
NAT. GAS
HIGH GAS
PRESSURE
SWITCH
PROPANE
HIGH GAS
PRESSURE
SWITCH
PROPANE
PRESSURE
REGULATOR
FEEDBACK LINE
NAT. GAS
PRESSURE
REGULATOR
FEEDBACK LINE
PROPANE
LOW GAS
PRESSURE
SWITCH
NAT. GAS LOW GAS
PRESSURE SWITCH
LEAK DETECTION
BALL VALVE
1/8" NPT PLUG
(INSTALL MANOMETER
HERE FOR HIGH GAS
PRESSURE TESTS)
NATURAL
GAS INLET
PROPANE
INLET
PROPANE
SSOV WITH
REGULATOR
NAT. GAS
SSOV WITH
REGULATOR
1/8" NPT PLUG
(INSTALL MANOMETER
HERE FOR NAT. GAS
LOW GAS PRESSURE
TEST)
1/8" NPT PLUG
(INSTALL MANOMETER
HERE FOR PROPANE
LOW GAS PRESSURE
TEST)
Figure 6-1
Low & High Gas Pressure Testing
6-1