Installation conditions, Wiring, Specifications – KEYENCE MS-F07 User Manual
Page 2: Output derating characteristic, Dimensions, Warranties and disclaimers, Installation conditions wiring specifications, Output derating characteristic dimensions, Installation orientation, Installation environment
![background image](/manuals/658150/2/background.png)
2
MS-E07/F07-IM_E
Copyright (c) 2011 KEYENCE CORPORATION. All rights reserved.
11797E 1081-1 96M11797 Printed in Japan
Installation orientation
Standard and upward installationis available as shown below.
Installation environment
• Install this unit indoors.
• Do not install this unit in locations exposed to direct sunlight.
• Do not install this unit in locations in which there is corrosive gas or flammable gas.
• Do not install this unit in locations exposed to a lot of dust, soot, or steam.
• Do not install this unit in locations in which water, oil, or chemicals may splash
onto the unit.
• When installing this unit in a location subject to vibration or impact, consider the
vibration proof mounting.
When installing this unit in a control console
• The ambient temperature for this unit should not exceed the upper temperature
limit (refer to the derating characteristic). When the upper temperature limit may
be exceeded, install a forced fan or cooler so that the ambient temperature is
below the upper temperature limit.
• Leave a sufficient ventilation space around this unit for heat dissipation.
• Do not install this unit just above a device with high heat generation (heater,
transformer, large-capacity resistor, etc.).
Selecting cables and crimp terminals
Terminals
Crimp terminals
Cables
Select cables with a wire diameter suited to the output rated current.
*1 For conforming to safety standards show above, rated input voltage is 100 to 240 VAC (50/60
Hz).
*2 Specified with the rated input voltage (100 or 200 VAC) and 100% load applied.
*3 The MS-F Series is a Zener-diode clamp type. The unit does not restart after the protection
circuit is activated.
(1) KEYENCE warrants the Products to be free of defects in materials and
workmanship for a period of one (1) year from the date of shipment. If any
models or samples were shown to Buyer, such models or samples were used
merely to illustrate the general type and quality of the Products and not to
represent that the Products would necessarily conform to said models or
samples. Any Products found to be defective must be shipped to KEYENCE
with all shipping costs paid by Buyer or offered to KEYENCE for inspection and
examination. Upon examination by KEYENCE, KEYENCE, at its sole option, will
refund the purchase price of, or repair or replace at no charge any Products
found to be defective. This warranty does not apply to any defects resulting
from any action of Buyer, including but not limited to improper installation,
improper interfacing, improper repair, unauthorized modification,
misapplication and mishandling, such as exposure to excessive current, heat,
coldness, moisture, vibration or outdoors air. Components which wear are not
warranted.
(2) KEYENCE is pleased to offer suggestions on the use of its various Products.
They are only suggestions, and it is Buyer's responsibility to ascertain the
fitness of the Products for Buyer’s intended use. KEYENCE will not be
responsible for any damages that may result from the use of the Products.
(3) The Products and any samples ("Products/Samples") supplied to Buyer are not
to be used internally in humans, for human transportation, as safety devices or
fail-safe systems, unless their written specifications state otherwise. Should any
Products/Samples be used in such a manner or misused in any way, KEYENCE
assumes no responsibility, and additionally Buyer will indemnify KEYENCE and
hold KEYENCE harmless from any liability or damage whatsoever arising out of
any misuse of the Products/Samples.
(4) OTHER THAN AS STATED HEREIN, THE PRODUCTS/SAMPLES ARE
PROVIDED WITH NO OTHER WARRANTIES WHATSOEVER. ALL
EXPRESS, IMPLIED, AND STATUTORY WARRANTIES, INCLUDING,
WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY,
FITNESS FOR A PARTICULAR PURPOSE, AND NON-INFRINGEMENT OF
PROPRIETARY RIGHTS, ARE EXPRESSLY DISCLAIMED.
IN NO EVENT SHALL KEYENCE AND ITS A FFILIATED ENTITIES BE
LIABLE TO ANY PERSON OR ENTITY FOR ANY DIRECT, INDIRECT,
INCIDENTAL, PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES
(INCLUDING, WITHOUT LIMITATION, ANY DAMAGES RESULTING FROM
LOSS OF USE, BUSINESS INTERRUPTION, LOSS OF INFORMATION, LOSS
OR INACCURACY OF DATA, LOSS OF PROFITS, LOSS OF SAVINGS, THE
COST OF PROCUREMENT OF SUBSTITUTED GOODS, SERVICES OR
TECHNOLOGIES, OR FOR ANY MATTER ARISING OUT OF OR IN
CONNECTION WITH THE USE OR INABILITY TO USE THE PRODUCTS,
EVEN IF KEYENCE OR ONE OF ITS AFFILIATED ENTITIES WAS ADVISED
OF A POSSIBLE THIRD PARTY’S CLAIM FOR DAMAGES OR ANY OTHER
CLAIM AGAINST BUYER. In some jurisdictions, some of the foregoing
warranty disclaimers or damage limitations may not apply.
BUYER'S TRANSFER OBLIGATIONS:
If the Products/Samples purchased by Buyer are to be resold or delivered to a
third party, Buyer must provide such third party with a copy of this document, all
specifications, manuals, catalogs, leaflets and written information provided to
Buyer pertaining to the Products/Samples.
E 1110-2
Installation Conditions
Wiring
Specifications
Model
MS-E07
MS-F07
In
p
u
t
co
ndi
ti
o
n
s
Input voltage
*1
85 to 264 VAC (50/60 Hz)
Efficiency
70 to 75% (typical)
Input current (100/200 VAC)
0.28/0.16 A max.
Leakage current (100/200 VAC)
0.5/1 mA max.
Rush current (100/200 VAC)
18/36 A max. (at 25°C (77°F) cold start)
Ou
tput
co
ndi
ti
o
n
s
Rated output voltage
5 VDC
12 VDC
Rated output current
1.5 A
0.65 A
Ripple/noise voltage
2% (p-p) max.
Starting time
*2
400 ms max.
Output holding time
20 ms min. (100 to 240 VAC)
Pr
o-
tect
ion
Overcurrent
1.9 A min.
0.79 A min.
Overvoltage
*3
Provided
Envir
o
n
m
e
n
ta
l r
e
sistan
ce
Ambient temperature
-10 to +60°C (14 to 140°F), No freezing
(Refer to the derating characteristic.)
Relative humidity
25 to 85%, No condensation
Ambient temperature for
storage
-20 to +70°C (-4 to 158°F), No freezing
Dielectric strength
3.0 kVAC, 50/60 Hz, 1 minute
(between input and output terminals),
2.0 kVAC, 50/60 Hz, 1 minute
(between input and FG terminals)
500 VDC, 1 minute.
(between output and FG terminals)
Shock immunity
300 m/s
2
in X, Y, and Z directions, 2 times
respectively
Vibration
10 to 55 Hz, 1.5 mm (max.) double amplitude
in X, Y, and Z directions,
2 hours respectively
(1 G max. when installed to DIN rail)
Insulation resistance
100 MΩ min. at 500 VDC
(between input and output terminals)
(between input and FG terminals)
(between output and FG terminals)
Applic
abl
e
Standar
d
Safety Standard
UL: UL60950-1
c-UL: CSA C22.2 No.60950-1
EN: EN60950-1
EMC Standard
FCC Part 15B Class A,
EN55011 Class A, EN61000-6-2
Weight
Approx. 140 g
Model
Screw size
Tightening torque
MS-E/F
M3
1.2N·m max.
7 mm max.
7 mm max.
Output Derating Characteristic
Dimensions
Warranties and Disclaimers
(14) (32) (50) (68) (86) (104) (122) (140) (158)
0
0
-10
10
20
30
40
50
60
70
10
20
30
40
50
60
70
80
90
100
Load factor (%)
Ambient temperature (°C (F°))
* The characteristic data shown above are
obtained when this unit is installed as
described in this Manual.
* The maximum rated load is limited to the out-
put derating characteristic. We recommend
that you use this unit under conditions in
which the average load factor is 70% or less.
22
9.5
80
30
8.6
8.6
7
70.7
75
35.4
72
Mounting hole
2 x ш5