beautypg.com

Sensor configuration – KEYENCE AP-C40(P) Series User Manual

Page 3

background image

3

Detection mode

Operating mode

Standard

Focus mode

High-speed

Zero shift input

Analog output

N.O./N.C.

2.5

msec

5

msec

100

msec

500

msec

General-purpose mode

Variable hysteresis mode

Window mode

Application mode 1

Application mode 2

Analog/zero shift

Standard

Eco mode

Power-save

Chatter prevention
Sets response time.

* F-1 and F-2 mode only

Values that fall between the P1 and P2
settings will be displayed in green,
while values outside that range will be
displayed in red.

When

A-1/A-2 is

selected

during
fixed mode
operation

When

operating

mode is

• Two-point tuning
• Active tuning

* High-speed mode provides a 1-ms

high-speed response.

Current value

Reference value

Hold value

Increase the
setting.
Decrease the
setting.

For other

than

Focus center pressure

After 4 sec

of no key

operation.

Reference value*

Press for 3 sec or more.

+

+

Toggling the
display

Manual configuration

Settings are
manually
configured. The
display changes
for each mode.
* Toggling the

display of
settings (see the
diagram below).

* Manual configuration

only during F-3/A-2
mode operation.

Current value

Peak hold

Bottom hold

* The reference value is

the pressure value when
zero shift input is
received and is replaced
only when zero shift
input is selected.

Mode
configuration

* See the Focus Mode section

of Part 10 for the center
pressures that can be
selected.

N.O.

N.O.

N.C.

N.C.

N.O.

N.C.

N.C.

N.O.

Control

output 1

Control

output 2

• N.O.

= normal open.

• N.C.

= normal close.

Display color (7-segment)

ON: Red, OFF: Green

ON: Green, OFF: Red

Normally red

Normally green
Within set value: Green
Outside set value: Red

(

)

9. Sensor Configuration

Toggling the display of settings

General-purpose mode/F1

Variable hysteresis mode/F-2

Window mode/F-3

Application mode 1/A-1

Application mode 2/A-2

Two-point tuning (F-1/F-2)

The sensor is made to detect the pressures when the target object is
present and then absent for confirmation of target suction pick-up, and
the intermediate value is used.
Control output 1 configuration: When P1 (H1) is selected on the settings
display.
Control output 2 configuration: When P2 (H2) is selected on the settings
display.

Flashes

for 3 sec.

Setting

Target object

present

Target object

absent

Active tuning (A-1)

See Section 11.

Note:• Press and hold the MODE button (

) for at least 3 seconds to return to the current

value/reference value/hold value display from each of the mode setting screens.

• Press the left side

on the manual adjustment button (

) while holding down the

mode button (

) to return to the previous display.

• The current value will be displayed based on the ambient pressure conditions prevalent

at that time without regard to zero shift input when the P2 setting display is selected for
A-1 mode or when the HI and Lo setting displays are selected for A-2 mode.

• The sensor must be configured manually when operating in the F-3/A-2 modes. The

SET button (

) will not function.