beautypg.com

Connection method and diagrams, Precautions for safe use, Detection mode operation – KEYENCE AP-C30WP User Manual

Page 2: Ap-ao1 panel mounting bracket, Analog output circuit, Zero shift input circuit, Connections input/output circuit

background image

2

AP-AO1 Panel mounting bracket

SE

T

AP

-C

33

MO

DE

MP

a

SE

T

AP

-C

40

MO

DE

MP

a

Panel mounting ring

Panel-mounted sample

Panel-mounted sample

Front protective
cover

Panel-mounted sample

5. Connection Method and Diagrams

Insert the included connector-tipped cable into the sensor’s connector.
Position the connector so that the side of the connector where the metallic
contacts are visible is facing up.

Connector cable

Side where the metallic

contacts are visible faces up.

Input/output circuit

Input/output circuit

(AP-C30W/C31W/C33W)

(AP-C30WP/C31WP/C33WP)

12 to 24 VDC

5 to 40 VDC

5 to 40 VDC

0V

Main circuit

Ov
ercurrent

protection circuit

Load

Load

Input/output

circuit

Analog output/
zero shift input: switchable

Brown

Blue

Black

White

Pink

12 to 24 VDC

0V

Main circuit

Ov
ercurrent

protection circuit

Input/output

circuit

Analog output/
zero shift input: switchable

Brown

Blue

Black

White

Pink

Load

Load

Analog output circuit

Analog
output (1 to 5 V)

0 V

Main

circuit

Blue

Pink

Zero shift input circuit

Zero shift input circuit

(AP-C30W/C31W/C33W)

(AP-C30WP/C31WP/C33WP)

(Short-circuit current 5 mA max.)

Main

circuit

Blue

Pink

12 to 24 VDC

Main

circuit

Pink

(Short-circuit current 5 mA max.)

Brown

Use non-contact input device such as open-collector.

6. Precautions for Safe Use

Follow these guidelines. Failure to do so may result in product damage.

CAUTION

Connections

Input/output circuit

Always ground the frame ground terminal when using an off-the-shelf
switching regulator.

Use separate conduits for power line and high voltage lines, since use
of a common conduit may result in device malfunction.

Improper wiring may result in the device becoming excessively hot or
in device damage.

Other

Do not use this sensor with corrosive gasses or liquids.

Do not insert objects such as wire into the pressure insertion area.
Doing so may result in the device failing to operate properly due to
damage to the pressure-sensitive elements.

Do not use sharp-tipped objects to press the setting keys.

7. Detection Mode Operation

General-purpose mode (F-1)

This mode allows the user to configure 2 detection points.
Control output 1: Turns ON when pressure exceeds setting P1.
Control output 2: Turns ON when pressure exceeds setting P2.

P1

0

Output 1

OFF

ON

OFF

P2

0

OFF

ON

OFF

Output 2

*Hysteresis is a standard 0.5% of F.S. when operating in general-pur-

pose mode and application modes 1 and 2. During focus mode op-
eration, it is 0.2% of F.S.

Variable hysteresis mode (F-2)

Two detection points may be user-configured, and hysteresis for both
may also be set.
Control output 1: Turns ON when pressure exceeds setting P1. Turns OFF

when pressure drops the selected hysteresis amount
below P1.

Control output 2: Turns ON when pressure exceeds setting P2. Turns OFF

when pressure drops the selected hysteresis amount
below P2.

P1

H1

Output 1

OFF

ON

OFF

0

P2

OFF

ON

OFF

H2

0

Output 2

Window mode (F-3)

The user may select a pair of upper (Hi) and lower (Lo) thresholds, and
the sensor turns OFF when the pressure falls outside of the resulting
range.
*Control output 1 is a standard 0.5% of F.S. During focus mode opera-

tion, it has a hysteresis of 0.2% of F.S., and control output 2 has a
hysteresis of 0.

Hi

Lo

Output1/Output2

OFF

ON

ON

OFF

OFF

0

Application mode 1 (A-1)

This detection mode is optimum for use in suction detection applica-
tions.
Recommended sensor heads: AP-C30W/C30WP/C31W/C31WP
Control output 1: Suction pressure detection.

Turns ON when pressure exceeds setting P1.

Control output 2: Detection and confirmation of vacuum burst pressure

detection (or vacuum ultimate pressure).
Turns ON when the pressure falls below setting P2.
*Cannot be used to detect vacuum burst pressure with

the AP-C31W/C31WP when operating in focus mode.
Standard mode operation only.

Zero shift:

The zero point is shifted immediately after the zero
shift timer is set following the activation of zero shift
input.

P1: Pressure setting for control output 1.
T1: Zero shift timer setting (ms) < Variable between 0 and 1,999 ms>
P2: Pressure setting for control output 2.
*P2 is unrelated to zero shift and is always based on the current ambi-

ent pressure.

P1

Output 1

OFF

ON

OFF

0

0

Output 2

OFF

ON

OFF

P2

0

0

Shift

Zero shift input

T1

Application mode 2 (A-2)

This mode is optimum for use in leak test applications.
Recommended sensor head: AP-C33W/C33WP
Control output 1: Leak pressure detection.

Turns ON when pressure falls below setting P1.
*Output only when receiving zero shift input.

Control output 2: Window comparator output for detection of fill pressure.

Turns OFF when pressure falls outside the range deter-
mined by upper (Hi) and lower (Lo) thresholds.
*Fill pressure values are displayed with the center pres-

sure as 0 during focus mode operation.

P1: Pressure setting for control output 1.
Hi: Upper threshold setting for control output 2.
Lo: Lower threshold setting for control output 2.
*The Hi and Lo values are unrelated to zero shift and are always based

on the current ambient pressure.

P1

Output1

Zero shift input

OFF

ON

OFF

ON

0

Hi

Lo

Output 2

OFF

ON

OFF

OFF

ON