beautypg.com

Vintage Cellars CC-CX8800 User Manual

Page 8

background image

Page 6 | 1-855-235-5271

CX 012014

Sizing the Unit to the Room

The specification chart will provide information on the units room size cooling capacity. There are circumstances in which a cellar design

may require a larger unit due to some existing design restrictions. In such a case, we recommend that the customer consider purchasing a

unit with a larger capacity to compensate for the design limitations. Issues such as glass doors, concrete, or brick walls and floors may seem

adequate but do not offer the insulation capacity required to maintain the optimum environment.

cx4400

1000

81

7

14.25” x 19.75” x 21.63”

cx8800

2000

101

10

16.25” x 22” x 22.25”

cx3300

650

76

5

14.25” x 19.75” x 21.63”

Model

Room Size

Weight

AMP’s

Product Dimensions

(cubic feet)

(lbs)

(running)

(W x H x D)

cx2200

300

55

3

14.25” x 13.25” x 16.38”

Temperature Delta - 30°F

(when exhaust environment does not exceed above 85°F and below 50°F)

Warranty - 2 yr parts & labor / 5 yr compressor only

Ventilation

The necessity of dissipating heat away from the unit is critical to the unit’s performance and cannot be overstated. As the unit operates

and cools, a greater amount of heat is generated on the exhaust side of the unit. Adequate ventilation is required in order to dissipate heat

away from the unit. If ventilation is inadequate, the exhaust will heat up and adversely affect the unit’s ability to cool.

Vapor Barrier

Vapor Barrier is REQUIRED to prevent the intrusion of water vapor so that the cellar can be kept at the correct temperature and humidity.

6 mm plastic sheeting (recommended) should be applied to the warm side of the cellar walls. The vapor barrier must also be applied to the

outside walls and ceiling. If it is impossible to reach the outside, then the plastic must be applied from within the cellar. The most common

method is to wrap the entire interior, leaving the plastic loose in the stud cavity so the insulation can be placed between each stud. All of

the walls and ceiling must be wrapped in plastic for a complete vapor barrier.

In areas of high humidity, such as Southern and Gulf States, the vapor barrier will prevent infiltration of warm moist air. The moist air can

cause mold to form, and standing water in drain pans promote microbial and fungal growth that cause unpleasant odors and indoor air

quality problems. If mold is found, remove it immediately and sanitize that portion of the unit.

Ambient Temperature Factor

The cooling system has the ability to cool a maximum of 30°F below the ambient temperature of the room it is exhausting to. Therefore, you

want to exhaust the unit in a room which will not exceed 85°F and preferably a consistent 75°F. Otherwise the unit will not have the capacity

to keep the wine at a desirable 55°F.

This manual is related to the following products: