VERSION 1 CONTROL FUNCTIONS
SET button
Display Set Point - press 1 sec
Modify Set Point - hold 3-5 sec
In programming mode it selects a
parameter or confirms an operation.
Up and Down Buttons
Use to adjust values or browse
parameter codes.
Defrost button
Manually start Defrost - hold 3-5 sec
SET button
Display Set Point - press 1 sec
Modify Set Point - hold 3-5 sec
In programming mode it selects a
parameter or confirms an operation.
Up and Down Buttons
Use to adjust values or browse
parameter codes.
Defrost button
Manually start Defrost - hold 3-5 sec
SET button
Display Set Point - press 1 sec
Modify Set Point - hold 3-5 sec
In programming mode it selects a
parameter or confirms an operation.
Up and Down Buttons
Use to adjust values or browse
parameter codes.
Defrost button
Manually start Defrost - hold 3-5 sec
SET button
Display Set Point - press 1 sec
Modify Set Point - hold 3-5 sec
In programming mode it selects a
parameter or confirms an operation.
Up and Down Buttons
Use to adjust values or browse
parameter codes.
Defrost button
Manually start Defrost - hold 3-5 sec
Set Point
The set point is set from the factory at 55°. It can be adjusted (hold SET button for 3-5 seconds) by the cus-
tomer between 50° and 67° in one degree increments.
The air probe is offset by three degrees so that the controller will think it is three degrees warmer than the
actual temperature. This allows the customer to set the thermostat at the temperature that they desire their
wine to be.
Defrost
After two hours of operation the controller will activate defrost. The compressor relay will de-energize, stop-
ping the compressor, evaporator fans, and condenser fans. The compressor relay will remain de-energized
for five minutes, then the unit will return to normal operation. “Df” will be displayed during defrost.
The Defrost cycle can be manually initiated by holding the Defrost button for 3-5 seconds.
Cooling Operation
Cooling is activated once the air sensor probe senses a temperature that is four degrees greater than the set
point. The controller then energizes the compressor relay which activates the compressor, evaporator fans
and condenser fans. The unit provides cooling until the air sensor probe senses the set point. At this point
the compressor relay is de-energized which stops the compressor, evaporator fans, and condenser fans.
Display
The air sensor probe temperature is displayed in °F to a resolution of 1°. The display will update immediately
on temperature decrease and 1° every 15 minutes on temperature increase. During the defrost cycle the
display will show “Df”.
Safety Features
Once the compressor relay is de-energized the controller must wait five minutes before re-energizing the
relay. This prevents the compressor from repeatedly turning off and on.
In the event of a faulty air sensor probe, the compressor will cycle on for 40 minutes and off for 10 minutes.
Alarms
The high temperature alarm (HA) will be displayed if the room temperature reaches 80 degrees.
The low temperature alarm (LA) will be displayed if the room temperature reaches 45 degrees.
The alarm will show 15 minutes after the detection of a temperature alarm condition.
P1 will be displayed in the event of a thermostat probe failure.
The alarms will not display for 99 minutes after the unit has turned on.
The alarms can be switched off by pushing any key on the controller.