VERSION 1 CONTROL FUNCTIONS

SET button

Display Set Point - press 1 sec

Modify Set Point - hold 3-5 sec

In programming mode it selects a

parameter or confirms an operation.

Up and Down Buttons

Use to adjust values or browse

parameter codes.

Defrost button

Manually start Defrost - hold 3-5 sec

SET button

Display Set Point - press 1 sec

Modify Set Point - hold 3-5 sec

In programming mode it selects a

parameter or confirms an operation.

Up and Down Buttons

Use to adjust values or browse

parameter codes.

Defrost button

Manually start Defrost - hold 3-5 sec

SET button

Display Set Point - press 1 sec

Modify Set Point - hold 3-5 sec

In programming mode it selects a

parameter or confirms an operation.

Up and Down Buttons

Use to adjust values or browse

parameter codes.

Defrost button

Manually start Defrost - hold 3-5 sec

SET button

Display Set Point - press 1 sec

Modify Set Point - hold 3-5 sec

In programming mode it selects a

parameter or confirms an operation.

Up and Down Buttons

Use to adjust values or browse

parameter codes.

Defrost button

Manually start Defrost - hold 3-5 sec

Set Point

The set point is set from the factory at 55°. It can be adjusted (hold SET button for 3-5 seconds) by the cus-

tomer between 50° and 67° in one degree increments.

The air probe is offset by three degrees so that the controller will think it is three degrees warmer than the

actual temperature. This allows the customer to set the thermostat at the temperature that they desire their

wine to be.

Defrost

After two hours of operation the controller will activate defrost. The compressor relay will de-energize, stop-

ping the compressor, evaporator fans, and condenser fans. The compressor relay will remain de-energized

for five minutes, then the unit will return to normal operation. “Df” will be displayed during defrost.

The Defrost cycle can be manually initiated by holding the Defrost button for 3-5 seconds.

Cooling Operation

Cooling is activated once the air sensor probe senses a temperature that is four degrees greater than the set

point. The controller then energizes the compressor relay which activates the compressor, evaporator fans

and condenser fans. The unit provides cooling until the air sensor probe senses the set point. At this point

the compressor relay is de-energized which stops the compressor, evaporator fans, and condenser fans.

Display

The air sensor probe temperature is displayed in °F to a resolution of 1°. The display will update immediately

on temperature decrease and 1° every 15 minutes on temperature increase. During the defrost cycle the

display will show “Df”.

Safety Features

Once the compressor relay is de-energized the controller must wait five minutes before re-energizing the

relay. This prevents the compressor from repeatedly turning off and on.

In the event of a faulty air sensor probe, the compressor will cycle on for 40 minutes and off for 10 minutes.

Alarms

The high temperature alarm (HA) will be displayed if the room temperature reaches 80 degrees.

The low temperature alarm (LA) will be displayed if the room temperature reaches 45 degrees.

The alarm will show 15 minutes after the detection of a temperature alarm condition.

P1 will be displayed in the event of a thermostat probe failure.

The alarms will not display for 99 minutes after the unit has turned on.

The alarms can be switched off by pushing any key on the controller.