SYSTEM OPERATION - VERSION 1 CONTROLLER

Initial Start-Up

When power is applied to the unit, the control will briefly display all symbols.

Normal System Cycle

After the unit or cellar has reached the set point, unit will turn off until temperature rises above set temperature (all units

are shipped with the set point of 55°F and a differential of 4°F).

Anti Short Cycle

The Anti Short Cycle ensures that the unit will remain off for a period of 5 minutes after the unit has reached the set point

to allow the pressure in the refrigeration system to equalize prior to starting the compressor.

Defrost Cycle

The Defrost Cycle is a precautionary measure, as icing or frosting of the coil does not occur during normal operation. The

system will go through a defrost cycle every 2 hours. During the defrost cycle, unit shuts down.

Air Sensor

Each cooling unit comes equipped with an air sensing probe. The air sensing probe senses the temperature of the cellar air

and cycles the unit on and off based on the desired cellar temperature.

Note: The desired cellar temperature is the temperature set by you.

Confirm if you have a Version 1 Controller using the above illustration

as a guide. If Your controller does not match this illustration than you

have a Version 2 Controller featured on page 12.