beautypg.com

Vintage Cellars CC-CX8800 User Manual

Page 7

background image

www.cellarcool.com | Page 5

Unobstructed Airflow

Unobstructed airflow to and from the unit is critical for the unit’s overall performance and life-span. A minimum

three-foot clearance (five foot is ideal) area is crucial. The air the fans blow needs to circulate and either dissi-

pate or absorb heat from the space, the more air to exchange the more efficient the unit will operate.

Note: Avoid attempting to camouflage the unit. This will restrict airflow and thus the unit’s ability to work efficiently.

Mounting the Unit

The unit must be mounted within 18“ of the top of the room in order to achieve sufficient cooling. As the room cools down, the

warm air will rise to the ceiling. Mounting the unit high in the room will create a consistently cool environment by capturing the

warm air and replacing it with cool air. Mounting the unit low in the room will result in a temperature variation in the room due

to the unit’s inability to draw warm air from the ceiling of the cellar to the unit itself, and cold air settling to the floor.

Door and Door Seal

An exterior grade (1 3/4”) door must be installed as a cellar

door. It is very important that weather stripping is at-

tached to all 4 sides of the doorjamb. A bottom “sweep” or

threshold is also required. The door must have a very good

seal to keep the cool cellar air from escaping out of the

cellar. One of the most common problems with cooling

units running continually is due to the door not sealing

properly. In cases where glass doors are used and the

room size is close to the recommended unit size, the

next larger size CellarCool should be used. This will

compensate for the insulation loss due to the lower insu-

lating rating of glass.

Wine Cellar

Exhaust Area

Keep Clear

Exhaust Fan/Vent

(optional)

Air Intake

(optional)

This manual is related to the following products: