Carrier 50TC User Manual

Page 8

background image

8

DETAIL “A”

PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING
UNIT ON ROOF CURB.

DUCT END

SEE DETAIL “A”

914 - 1371

( 36” - 54” )

“B”

“A”

“C”

C10774

UNIT

MAX WEIGHT

DIMENSIONS

A

B

C

LB

KG

IN

MM

IN

MM

IN

MM

50TC---D16

2010

912

116.0

2945

57.5

1461

59.5

1510

NOTES:

1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around

the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 5 -- Rigging Details

Positioning on Curb —

For full perimeter curbs CRRFCURB074A00 and 075A00,

the clearance between the roof curb and the front and rear

base rails should be

1

/

4

in (6.4 mm). The clearance between

the curb and the end base rails should be

1

/

2

in (13 mm). For

retrofit applications with curbs CRRFCURB003A01 and

4A01, the unit should be position as shown in Fig. 6.

Maintain the 15.5 in (394 mm) and 8

5

/

8

in (220 mm)

clearances and allow the 22

5

/

16

in (567 mm) dimension to

float if necessary.

C10003

Fig. 6 -- Retrofit Installation Dimensions

If the alternative condensate drain location through the

bottom of the unit is used in conjunction with a retrofit

curb, the hole in the curb must be moved 12.5 in (320

mm) towards the duct end of the unit. (See Fig. 7.)

Although unit is weatherproof, guard against water from

higher level runoff and overhangs.

Original
Position

New Position
(moved 12.5 in.)

C10904

Fig. 7 -- Alternative Condensate Drain Hole Positions

IMPORTANT:

If the unit has the factory--installed Thru--the--Base
option, make sure to complete installation of the option
before placing the unit on the roof curb.
See the following section:

S

Factory--Option Thru--Base Connections
on page 15

NOTE: If electrical connections is not going to occur at
this time, tape or otherwise cover the fittings so that
moisture does not get into the building or conduit in the
interim.

Remove all shipping materials and top skid. Remove extra

center post from the condenser end of the unit so that the

condenser end of the unit matches Fig. 17 -- 19. Recycle

or dispose of all shipping materials.

50TC

--