beautypg.com

Warning, Step 9 — install external condensate trap and line, Step 10 — make electrical connections – Carrier 50TC User Manual

Page 11

background image

11

Step 9 — Install External Condensate Trap and

Line

The unit has one

3

/

4

-in. condensate drain connection on

the end of the condensate pan and an alternate connection

on the bottom. See Fig. 15. Unit airflow configuration

does not determine which drain connection to use. Either

drain connection can be used with vertical or horizontal

applications.

When using the standard side drain connection, ensure the

red plug in the alternate bottom connection is tight. Do

this before setting the unit in place. The red drain pan can

be tightened with a

1

/

2

--in. square socket drive extension.

To use the alternate bottom drain connection, remove the

red drain plug from the bottom connection (use a

1

/

2

--in.

square socket drive extension) and install it in the side

drain connection.

DRAIN

(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARD

SIDE DRAIN

ALTERNATE

BOTTOM DRAIN

C08021

Fig. 15 -- Condensate Drain Pan (Side View)

The piping for the condensate drain and external trap can

be completed after the unit is in place. See Fig. 16.

NOTE: Trap should be deep enough to offset maximum unit static

difference. A 4” (102) trap is recommended

.

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE

BASE RAIL

OPEN

VENT

TO ROOF

DRAIN

DRAIN PLUG

ROOF

CURB

SEE NOTE

2˝ (51) MIN

C08022

Fig. 16 -- Condensate Drain Piping Details

All units must have an external trap for condensate

drainage. Install a trap at least 4-in. (102 mm) deep and

protect against freeze-up. If drain line is installed

downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do

not use a pipe size smaller than the unit connection

(

3

/

4

-in.).

Step 10 — Make Electrical Connections

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Unit cabinet must have an uninterrupted, unbroken

electrical ground to minimize the possibility of personal

injury if an electrical fault should occur. This ground may

consist of electrical wire connected to unit ground lug in

control compartment, or conduit approved for electrical

ground when installed in accordance with NEC (National

Electrical Code); ANSI/NFPA 70, latest edition (in

Canada, Canadian Electrical Code CSA [Canadian

Standards Association] C22.1), and local electrical codes.

!

WARNING

NOTE: Field--supplied wiring shall conform with the
limitations of minimum 63_F (33_C) rise.
Field Power Supply —

For those units without through--the--curb power, conduit

must be used to route the main power from the condenser

end, via the power entry in the corner post of the unit (see

Figs. 17, 18 and 19) to either the factory option disconnect

or the bottom of the control box. 1” conduit is provided

wrapped around compressor. A second conduit is provided

with factory installed powered convenience outlet. For those

units that require conduit larger than 1”, it must be field

supplied. Figs. 17, 18 and 19 show the various wire routings.

C10010

Fig. 17 -- Conduit into Factory Option Disconnect

C10011

Fig. 18 -- Conduit into Control Box

50TC

--

*16