Smoke detectors – Carrier 50TC User Manual

Page 41

background image

41

To wire the return air enthalpy sensor, perform the

following:

1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable

to connect the return air enthalpy sensor to the enthal-

py controller.

2. Connect the field--supplied RED wire to (+) spade con-

nector on the return air enthalpy sensor and the (+) ter-

minal on the enthalpy controller. Connect the BLK wire

to (--) spade connector on the return air enthalpy sensor

and the (--) terminal on the enthalpy controller.

Smoke Detectors

Smoke detectors are available as factory--installed options on

50TC--D16 units. Smoke detectors may be specified for

Supply Air only or for Return Air without or with

economizer or in combination of Supply Air and Return Air.

Return Air smoke detectors are arranged for vertical return

configurations only. All components necessary for operation

are

factory--provided

and

mounted.

The

unit

is

factory--configured for immediate smoke detector shutdown

operation; additional wiring or modifications to unit terminal

board may be necessary to complete the unit and smoke

detector configuration to meet project requirements.

Units equipped with factory--optional Return Air smoke

detectors require a relocation of the sensor module at unit

installation. See “Completing Installation of Return Air

Smoke Sensor:” on page 43 for details.

System —

The smoke detector system consists of a four--wire

controller and one or two sensors. Its primary function is

to shut down the rooftop unit in order to prevent smoke

from circulating throughout the building. It is not to be

used as a life saving device.

Controller —

The controller (see Fig. 76) includes a controller housing,

a printed circuit board, and a clear plastic cover. The

controller can be connected to one or two compatible duct

smoke sensors. The clear plastic cover is secured to the

housing with a single captive screw for easy access to the

wiring terminals. The controller has three LEDs (for

Power, Trouble and Alarm) and a manual test/reset button,

all located on the cover face.

Sensor Module —

The sensor module (see Fig. 77) includes a plastic housing, a

printed circuit board, a clear plastic cover, a sampling tube

inlet and an exhaust tube. The sampling tube (when used)

and exhaust tube are attached during installation. The

sampling tube varies in length depending on the size of the

rooftop unit. The clear plastic cover permits visual

inspections without having to disassemble the sensor. The

cover attaches to the sensor housing using four captive

screws and forms an airtight chamber around the sensing

electronics. Each sensor includes a harness with an RJ45

terminal for connecting to the controller. Each sensor has

four LEDs (for Power, Trouble, Alarm and Dirty) and a

manual test/reset button (on the left--side of the housing).

Duct smoke sensor

controller

Fastener

(2X)

Controller cover

Conduit nuts

(supplied by installer)

Conduit support plate

Cover gasket

(ordering option)

Conduit couplings

(supplied by installer)

Terminal block cover

Controller housing

and electronics

Alarm

Power

Test/reset
switch

Trouble

C08208

Fig. 76 -- Controller Assembly

Duct smoke sensor

See

Detail A

Exhaust tube

Plug

Sampling tube

(ordered separately)

Intake

gasket

Cover gasket

(ordering option)

TSD-CO2

(ordering option)

Sensor housing
and electronics

Exhaust gasket

Coupling

Sensor cover

Detail A

Magnetic
test/reset

switch

Alarm

Trouble

Power
Dirty

C08209

Fig. 77 -- Smoke Detector Sensor Module

50TC

--

*16