Space Sensors —

The PremierLink controller is factory--shipped configured for

Space Sensor Mode. A Carrier T--55 or T--56 space sensor

must be used. T--55 space temperature sensor provides a

signal of space temperature to the PremierLink control. T--56

provides same space temperature signal plus it allows for

adjustment of space temperature setpoints from the face of

the sensor by the occupants.

2

3

4

5

6

1

SW1

SEN

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

C08201

Fig. 44 -- T--55 Space Temperature Sensor Wiring

Connect T--55: See Fig. 44 for typical T--55 internal

connections. Connect the T--55 SEN terminals to TB3

terminals 1 and 3 (see Fig. 45).

SEN

J6-7

J6-6

1

3

TB3

PL

SEN

C10023

Fig. 45 -- PremierLink T--55 Sensor

Connect T--56: See Fig. 46 for T--56 internal connections.

Install a jumper between SEN and SET terminals as

illustrated. Connect T--56 terminals to TB3 terminals 1, 3

and 5 (see Fig. 47).

2

3

4

5

6

1

SW1

SEN

SET

Cool

Warm

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

JUMPER
TERMINALS
AS SHOWN

BLK
(T56)

C08202

Fig. 46 -- T--56 Internal Connections

SEN

J6-7

J6-6

1

3

TB3

PL

SEN

SET

Jumper

TB3

PL

J6-5

5

SET

C10022

Fig. 47 -- PremierLink T--56 Sensor

Connect Thermostat —

A 7--wire thermostat connection requires a 24--v power

source and a common connection. Use the R and C

terminals on the CTB’s THERMOSTAT connection strip

for these. Connect the thermostat’s Y1, Y2, W1, W2 and

G terminals to PremierLink TB3 as shown in Fig. 48.

If the 50TC--D16 unit is equipped with factory--installed

smoke detector(s), disconnect the factory BLU lead at

TB3--6 (Y2) before connecting the thermostat. Identify the

BLU lead originating at CTB--DDC--1; disconnect at

TB3--6 and tape off. Confirm that the second BLU lead at

TB3--6 remains connected to PremierLink J4--8.

G

J4-12

J4-10

J4-8

Y1

Y2

2

R

R

4

6

J4-6

J4-4

W2

C

8

10

C

SPACE

THERMOSTAT

CTB

THERMOSTAT

PL

W1

TB3

CTB

THERMOSTAT

C10283

Fig. 48 -- Space Thermostat Connections

If the 50TC--D16 unit has an economizer system and

free--cooling operation is required, a sensor representing

Return Air Temperature must also be connected

(field--supplied and installed). This sensor may be a T--55

Space Sensor (see Fig. 44) installed in the space or in the

return duct, or it may be sensor PNO 33ZCSENSAT,

installed in the return duct. Connect this sensor to TB3--1

and TB3--3 per Fig. 45.

Configure the unit for Thermostat Mode —

Connect to the CCN bus using a CCN service tool and

navigate to PremierLink Configuration screen for Operating

Mode. Default setting is Sensor Mode (value 1). Change the

value to 0 to reconfigure the controller for Thermostat Mode.

When the PremierLink is configured for Thermostat

Mode, these functions are not available: Fire Shutdown

(FSD), Remote Occupied (RMTOCC), Compressor Safety

(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure

Switch (FILTER).

50TC

--

*16