Operators instructions
CombiPress™, type PFMx

ATEX Gas ia and for ATEX Dust ia

For ATEX ia Gas zone 0 and ATEX ia Dust zone 20 a zener barrier must separate the hazardous and safe area and must be in-
stalled in accordance with prevailing guidelines for zone 0 / zone 20.

ATEX ia Gas / Dust data:
Approval: Gas Zone 0/1

II 1 G, Ex ia IIC T5 Ga

Dust Zone 20/21

II 1 D, Ex ia IIIC T100°C Da

Voltage drop

U

Disp

4,5 or 6,5 VDC

Temperature class T1…T5 Zone 0 and 20

-20°C…60°C

Zone 1/2 and 21/22 -40°C…65°C

Internal inductivity

L

i

<10 µH

Internal capacity

C

i

<15 nF


Barrier data

U

i

<30 VDC

I

i

<0,1 A

P

i

<0,75 W

Suitable barrier

e.g.: Pepperl+Fuchs, Z728

The display is supplied via the UnitCom from the transmitter. However to make the transmitter/display intrinsic safe a zener barrier
must be inserted before the PFMx/DFON. As the CombiView

, type DFON is attached to a Baumer PFMx transmitter using the

UnitCom ribbon cable, it is considered to be an integrated part of the instrument.

If the relays are enabled, each relay must be protected by a zener barrier. Use a barrier for each relay or a barrier with multiple
channels. However the two relays must have each a barrier.

Barrier data U

<30 VDC

I

<75 mA

P

<0,75 W

Suitable barrier

e.g.: Pepperl+Fuchs, Z779

Electrical connection

PFMx without relay output

PFMx with relay output

1 +

2 -

Zener
barrier

15…30 VDC

1 +

2 -

3

4

5

6

15…30 VDC

Zener
barrier

Zener
barrier

Zener
barrier

0…30 VDC
75 mA

0…30 VDC
75 mA

Relay 2

Relay 1

Operators instructions: 11120948 PFMx Page 9 / 12