Operators instructions combipress™, type pfmx, Atex gas na – Baumer CombiPress PFMH User Manual

Page 10

background image

www.baumer.com

Operators instructions
CombiPress™, type PFMx

ATEX Gas nA

For ATEX nA zone 2 is approved without using zener barrier to separate the hazardous and safe area and must be installed in
accordance with prevailing guidelines for zone 0.

ATEX data:

Approval: Gas Zone 2

II 3 G, Ex nA II T5

Voltage drop

U

Disp

4,5 or 6,5 VDC

Temperature class T1…T5 -30 < T

amb

<65°C

Internal inductivity

L

i

<10 µH

Internal capacity

Ci

<15 nF

Maximum voltage

U

max

<35 VDC

Maximum current

I

max

<0,1 A

1 +

2 -

3

4

5

6

4…20 mA

Display without relay output

Display with relay output

4…20 mA

1 +

2 -

Relay 1

Relay 2

Programming the CombiPress™ w./w.o. DFON in ATEX area

Programming the CombiPress

and the CombiView

, in hazardous area with the FlexProgrammer is not allowed, as the FlexPro-

grammer (and/or the PC) is not ATEX approved for use in hazardous area.

Follow below procedure to programme the instrument:

a

Disconnect mains from the 4…20 mA loop circuit

b

Disconnect the instrument from the circuit within the hazardous area

c

Uninstall the instrument and bring it to safe area

d

Connect the FlexProgrammer and perform the configuration session.

e

Re-install the instrument in the hazardous area

f

Connect the instrument to the circuit

g

Connect mains from the 4…20 mA loop circuit

Operators instructions: 11120948 PFMx Page 10 / 12