Kyle, Form 5 control operator panel, Led indicators – Cooper Lighting S280-79-10 User Manual

Page 7: Figure 5. form 5 control operator panel

background image

Form 5 Control Operator Panel

The Form 5 control operator panel (Figure 8) allows local
operation and status interrogation through built-in operator
controls and status displays. The operator panel contains
LED indicators, operational pushbuttons, membrane-type
functional/indication switches, backlit LCD display, and
Hot Line Tag switch with indication. An RS-232 port is also
provided to permit the temporary connection of a PC for
programming the parameters in the control.

All indicators with the exception of Hot Line Tag and
recloser status are automatically turned off after 5 minutes
of operator panel inactivity.

Reactivating is accomplished by pressing any operation
switch. The LCD messages will remain while in this
power-saving mode, although the illuminating backlight
will shut off.

LED Indicators

The operator panel LED indicators (Figure 5) give instant
information on the control and recloser status.

LED indicators include:

CONTROL OK

This green LED is illuminated when the continuous self-
diagnostics of the control have detected no CPU or mem-
ory malfunctions and indicate that the control is capable of
normal operation.

AC POWER

This green LED is illuminated when the presence of ac
input power to the control is sensed. The LED will turn off
if ac power is lost for more than 10 seconds.

ABOVE MIN TRIP

This red LED is illuminated when the control detects that
current is above the programmed minimum trip value for
Bushings 1-2, Bushings 3-4, Bushings 5-6, Ground, or
Sensitive Ground.

CHECK BATTERY

This red indicator illuminates for two conditions:

1. Battery voltage is below 20 Vdc or drops 2Vdc or more

during battery test.

2. The control fails a manual battery test. The LED will

remain on until a successful battery test is completed.

Refer to the Battery Test Procedure in this manual for
more information.

RECLOSER MALFUNCTION

This red indicator is illuminated when the control detects
a failure in a trip or close operation. It turns off automati-
cally if the recloser returns to the proper state.

REVERSE POWER FLOW

This red indicator illuminates when the control detects
power flow from the load side to the source side of the
recloser.

Note:

Voltage sensor polarity and phase must be correct for
reverse power flow to function properly.

BUSHINGS 1-2 FAULT TARGET

BUSHINGS 3-4 FAULT TARGET

BUSHINGS 5-6 FAULT TARGET

GROUND FAULT TARGET

SENSITIVE GROUND FAULT TARGET

These red target LEDs illuminate when the control issues
an overcurrent trip signal while the respective phase cur-
rent or ground current exceeds the minimum pickup
value. Reset is accomplished automatically when Auto
Reset is activated and a successful close operation is per-
formed or manual reset is accomplished by pressing the
RESET TARGETS button on the control operator panel.

BUSHINGS 1-2 VOLTAGE

BUSHINGS 3-4 VOLTAGE

BUSHINGS 5-6 VOLTAGE

These red voltage LEDs illuminate when the control
detects the presence of voltage on the respective bush-
ings as connected to TB1. Refer to the Customer Con-
nections for AC Power
section in these instructions to
determine the appropriate power connections.

RECLOSER CLOSED

This red indicator is illuminated when the control senses
that the recloser mechanism is in the closed position.

S280-79-10

7

!

SAFETY

FOR LIFE

Figure 5.
Form 5 control operator panel.

CONTROL OK

AC POWER

ABOVE MIN TRIP

REVERSE POWER FLOW

RECLOSER MALFUNCTION

CHECK BATTERY

BUSHINGS 1-2 FAULT TARGET

BUSHINGS 3-4 FAULT TARGET

BUSHINGS 5-6 FAULT TARGET

GROUND FAULT TARGET

SENSITIVE-GROUND FAULT TARGET

BUSHINGS 1-2 VOLTAGE

BUSHINGS 3-4 VOLTAGE

BUSHINGS 5-6 VOLTAGE

RECLOSER CLOSED

RECLOSER OPEN

CONTROL LOCKOUT

BACK

NEXT

LAMP
TEST

CHANGE

RESET

TARGETS

RESET

MAX CURRENT

GND TRIP
BLOCKED

NON

RECLOSING

SUPERVISORY

BLOCKED

COLD LOAD

PICK UP

BLOCKED

BATTERY

TEST

FAST

TRIPS

DISABLED

ALTERNATE

PROFILE

NO. 1

ALTERNATE

PROFILE

NO. 2

ALTERNATE

PROFILE

NO. 3

HOT LINE

TAG

ON

OFF

TX 3

RX 3

CLOSE

TRIP

(LOCKOUT)

KYLE

®

FORM 5

RECLOSER CONTROL

RS232

TX 2

RX 2