Cooper Lighting S280-79-10 User Manual
Page 51

S280-79-10
51
!
SAFETY
FOR LIFE
Form 5 Control Default Test Optimal Values
2.
Volts
28.0
2.6 Volts
28.0
Battery Circuitry
MA
35
2.6 MA
550
Volts
27.0
2.6 volts
24.2
3.
Normal Profile
Phase A Amps
Phase B Amps
Phase C Amps
100.5
100.3
100.7
Phase
Profile #1
Phase A Amps
Phase B Amps
Phase C Amps
Minimum Trip
200.9
200.2
200.5
Profile #2
Phase A Amps
Phase B Amps
Phase C Amps
200.9
200.2
200.5
Profile #3
Phase A Amps
Phase B Amps
Phase C Amps
200.9
200.2
200.5
4.
Normal
Ground Amps
50.1
Ground
Profile #1
Ground Amps
100.3
Minimum Trip
Profile #2
Ground Amps
100.3
Profile #3
Ground Amps
100.3
5.
Trip to Lockout Sequence
1st
2nd
3rd
4th
Phase Timing
Normal
Phase A 2X
0.161
0.164
1.416
1.421
Phase B 5X
0.018
0.017
0.278
0.280
Phase C 10X
0.016
0.014
0.088
0.086
Profile #1
Phase A 2X
0.153
0.154
1.443
1.441
Phase B 5X
0.015
0.014
0.273
0.275
Phase C 10X
0.011
0.009
0.087
0.087
Profile #2
Phase A 2X
0.153
0.154
1.443
1.441
Phase B 5X
0.015
0.014
0.273
0.275
Phase C 10X
0.011
0.009
0.087
0.087
Profile #3
Phase A 2X
0.153
0.154
1.443
1.441
Phase B 5X
0.015
0.014
0.273
0.275
Phase C 10X
0.011
0.009
0.087
0.087