beautypg.com

Cooper Lighting S280-79-10 User Manual

Page 51

background image

S280-79-10

51

!

SAFETY

FOR LIFE

Form 5 Control Default Test Optimal Values

2.

Volts

28.0

2.6 Volts

28.0

Battery Circuitry

MA

35

2.6 MA

550

Volts

27.0

2.6 volts

24.2

3.

Normal Profile

Phase A Amps

Phase B Amps

Phase C Amps

100.5

100.3

100.7

Phase

Profile #1

Phase A Amps

Phase B Amps

Phase C Amps

Minimum Trip

200.9

200.2

200.5

Profile #2

Phase A Amps

Phase B Amps

Phase C Amps

200.9

200.2

200.5

Profile #3

Phase A Amps

Phase B Amps

Phase C Amps

200.9

200.2

200.5

4.

Normal

Ground Amps

50.1

Ground

Profile #1

Ground Amps

100.3

Minimum Trip

Profile #2

Ground Amps

100.3

Profile #3

Ground Amps

100.3

5.

Trip to Lockout Sequence

1st

2nd

3rd

4th

Phase Timing

Normal

Phase A 2X

0.161

0.164

1.416

1.421

Phase B 5X

0.018

0.017

0.278

0.280

Phase C 10X

0.016

0.014

0.088

0.086

Profile #1

Phase A 2X

0.153

0.154

1.443

1.441

Phase B 5X

0.015

0.014

0.273

0.275

Phase C 10X

0.011

0.009

0.087

0.087

Profile #2

Phase A 2X

0.153

0.154

1.443

1.441

Phase B 5X

0.015

0.014

0.273

0.275

Phase C 10X

0.011

0.009

0.087

0.087

Profile #3

Phase A 2X

0.153

0.154

1.443

1.441

Phase B 5X

0.015

0.014

0.273

0.275

Phase C 10X

0.011

0.009

0.087

0.087