Installation of a Form 5 control with a remote supply volt-
age transformer must include the following:

• Protection of the recloser bushings and the supplying

transformer with lightning arresters.

• Grounding of the recloser head and tank.

• Grounding of the transformer tank.

• Grounding of the control cabinet.

• Grounding of the SCADA equipment

Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions

36

Surge
Arrester

Recloser
Head
Ground

Supply

Voltage

Pole

Ground

Pole

Recloser

Pole

Surge
Arrester

Transformer

Arrester

Ground

Form 5 LS Control

HOT

NEU

GND

NEU AC

Input Terminal Block

Control Cable

Surge
Arrester

Arrester
Ground

Customer Ground Connection
at External Lug

AC

NEUTRAL

Form 5 LS Control

Supply Voltage

Transformer

ELECTRICAL CONNECTIONS - Remote dedicated

supply transformer

Form 5 LS Control

AC

NEUTRAL

Input
Terminal
Block

115 Vac
Supply Voltage

Local Isolation
Transformer

ELECTRICAL CONNECTIONS - using isolation transformer

Customer
Supplied
Low Voltage

External
Ground Lug

Low Voltage
Arrester

Note: Distance between

transformer and
recloser should be
one pole span or
less

System

Neutral

External

Ground Lug

Input

Terminal

Block

Low Voltage Distribution Network

Figure 30.
Recommended grounding method for the Form 5 Control installed on 4-wire multi-grounded, 3-wire
ungrounded, or impedance-grounded systems with remote supply voltage transformer.

IMPORTANT: All external inputs to the Form 5 con-
trol must be routed within 8 inches of their correspond-
ing ground. During a surge, a potential of
approximately 1.5kV per foot can develop in the con-
ductors. Differences between conductor and ground
path lengths can add additional stress to the control
components in the event of a power surge.

IMPORTANT: In pole-mounted applications, a
ground connection must be made between the
recloser, transformer, recloser control, and SCADA
equipment for proper protection of the equipment. The
pole ground must be sized per local utility practices to
minimize the impedance between the recloser and the
control.

Grounding with a Remote Supply Voltage Transformer; 4-Wire Multi-Grounded,
3-Wire Ungrounded, or Impedance-Grounded