Standard and UDP Controls

Standard and UDP Form 5 control DIF inputs and outputs
are described in the following pages.

Maximum Switching Voltage: . . . . . 135 Vac 110 Vdc

Maximum Switching Loading: . . . . . 600 mA

Maximum Pickup-Release Time: . . 3 msec (does not count control response time)

Input Protection: . . . . . . . . . . . . . . . Shunting type using MOVs and capacitors

Minimum Detection Level: . . . . . . . . . . . . . . . . . . . . . . . . 8 Vac

(50 or 60Hz)

10 Vdc

Maximum Operating Voltage: . . . . . . . . . . . . . . . . . . . . . 135 Vac

(50 or 60Hz)

175 Vdc

Input Impedance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 k minimum (inputs are current limited)

Maximum Input Loading: . . . . . . . . . . . . . . . . . . . . . . . . . 2 mA per input

Maximum Leakage Rejection: . . . . . . . . . . . . . . . . . . . . . 1 mA

Maximum Pickup Time: . . . . . . . . . . . . . . . . . . . . . . . . . . 10 msec (does not count control response time)

Minimum Input Pulse Time: . . . . . . . . . . . . . . . . . . . . . . . 100 msec

Minimum Transition Time between Pulse Inputs: . . . . . . 200 msec

Input Protection: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shunting type using MOVs and capacitors.

Opto Isolation from input to system.

Voltage Level: . . . . . 28 Vdc (nominal)

Output Current: . . . . 30 mA maximum

TABLE 1
DIF Input Ratings

TABLE 2
Whetting Voltage Source
(Supplied by Internal Voltage Source of DIF Module)

TABLE 3
DIF Output Ratings

IMPORTANT: Each DIF contains a small, isolated
current source for use with external dry contacts. This
supply is intended for use with the DIF inputs only and
must not be used for powering external circuits. This is
considered a dry contact input for customer connection.